Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
Table 51. Bypass—P17
Code Parameter Min. Max. Unit Default ID Note
P17.1
12
Bypass Enable 0 1418 0 = Disabled
1 = Enabled
P17.2
12
Bypass Start Delay 1 32765 s 5 544
P17.3
12
Auto Bypass 0 542 0 = Disabled
1 = Enabled
P17.4
12
Auto Bypass Delay 0 32765 s 10 543
P17.5
12
Overcurrent Bypass Enable 0 547 0 = Disabled
1 = Enabled
P17.6
12
IGBT Fault Bypass Enable 0 546 0 = Disabled
1 = Enabled
P17.7
12
4 mA Fault Bypass Enable 0 548 0 = Disabled
1 = Enabled
P17.8
12
Undervoltage Bypass Enable 0 545 0 = Disabled
1 = Enabled
P17.9
12
Overvoltage Bypass Enable 0 549 0 = Disabled
1 = Enabled
Table 52. Multi-Pump Control—P18
Code Parameter Min. Max. Unit Default ID Note
P18.1
12
Number of Motors 1 5 1 342
P18.2
2
Bandwidth 0.0 100.0 % 10.0 343
P18.3
2
Bandwidth Delay 0 3600 s 10 344
P18.4
2
Interlock Enable 1 350 0 = Disabled
1 = Enabled
P18.5
2
Include Freq Converter 1 346 0 = Disabled
1 = Enabled
P18.6
2
Auto-Change Enable 0 345 0 = Disabled
1 = Enabled
P18.7
2
Auto-Change Interval 0.0 3000.0 h 48.0 347
P18.8
2
Auto-Change Freq Limit Par. P1.1 Par. P1.2 Hz 25.00 349
P18.9
2
Auto-Change Motor Limit 0 5 1 348
P18.10
12
Damper Start 0 483 0 = Normal
1 = Interlock Start
2 = Interlock Tout
3 = Interlock Delay
P18.11
12
Damper Time Out 1 32500 s 5 484
P18.12
12
Damper Delay 1 32500 s 5 485