Table 47. Preset Speed—P12
Code Parameter Min. Max. Unit Default ID Note
P12.1
2
Preset Speed 1 0.00 Par. P1.2 Hz 5.00 105
P12.2
2
Preset Speed 2 0.00 Par. P1.2 Hz 10.00 106
P12.3
2
Preset Speed 3 0.00 Par. P1.2 Hz 15.00 118
P12.4
2
Preset Speed 4 0.00 Par. P1.2 Hz 20.00 119
P12.5
2
Preset Speed 5 0.00 Par. P1.2 Hz 25.00 120
P12.6
2
Preset Speed 6 0.00 Par. P1.2 Hz 30.00 121
P12.7
2
Preset Speed 7 0.00 Par. P1.2 Hz 35.00 122
Table 48. Brake—P14
Code Parameter Min. Max. Unit Default ID Note
P14.1
12
DC-Brake Current Drive Nom
CT*15/100
Drive Nom
CT*15/10
ADrive Nom
CT*1/2
254
P14.2
12
Start DC-Brake Time 0.00 600.00 s 0.00 263
P14.3
12
Stop DC-Brake Frequency 0.10 10.00 Hz 1.50 262
P14.4
12
Stop DC-Brake Time 0.00 600.00 s 0.00 255
P14.5
12
Brake Chopper 0 251 0 = Disabled
1 = B(Run) T(Rdy)
2 = External
3 = B(Rdy) T(Rdy)
4 = B(Run) T(No)
P14.6
12
Flux Brake 0 266 0 = Off
1 = On
P14.7
12
Flux Brake Current Active Motor
Nom I*1/10
Par. P8.2 A Active Motor
Nom I*1/2
265
Table 49. Fire Mode—P15
Code Parameter Min. Max. Unit Default ID Note
P15.1
12
Fire Mode Function 0 535 0 = Closing Contact
1 = Opening Contact
P15.2
12
Fire Mode Ref Select
Function
0 536 0 = Disabled
1 = Enabled
P15.3
2
Fire Mode Min Frequency Par. P1.1 Par. P1.2 Hz 15.00 537
P15.4
2
Fire Mode Freq Ref 1 0.0 100.0 % 75.0 565
P15.5
2
Fire Mode Freq Ref 2 0.0 100.0 % 100.0 564
P15.6
12
Smoke Purge Frequency 0.0 100.0 % 50.0 554
Table 50. Second Motor Parameter—P16
Code Parameter Min. Max. Unit Default ID Note
P16.1
1
Motor Nom Current 2 Drive Nom
CT*1/10
Drive Nom
CT*1/10
A Drive Nom CT 577
P16.2
1
Motor Nom Speed 2 300 20000 rpm 2nd Motor Nom
Speed
578
P16.3
1
Motor PF 2 0.30 1.00 0.85 579
P16.4
1
Motor Nom Volt 2 180 690 V 2nd Motor Nom V 580
P16.5
1
Motor Nom Freq 2 8.00 400.00 Hz 2nd Motor Nom Freq 581