Firmware Manual

Appendix A—Description of Parameters
PowerXL DG1 Series Adjustable Frequency Drives MN040004EN—March 2014 www.eaton.com 183
P19.26 511 Timer 1 Duration 2, 3, 4 RW
The timer will run when activated by DI).
P19.27 532 Timer 1 Channel 2, 3, 4 RW
Select affected time channel.
0 Not used
1 Time channel 1
2 Time channel 2
3 Time channel 3
P19.28 513 Timer 2 Duration 2, 3, 4 RW
See P19.26.
P19.29 533 Timer 2 Channel 2, 3, 4 RW
SeeP19.27.
P19.30 515 Timer 3 Duration 2, 3, 4 RW
See P19.26.
P19.31 534 Timer 3 Channel 2, 3, 4 RW
See P19.27.
P20.1.1 1556 FB Data Output 1 Sel 1,2, 3, 4 RW
Selects fieldbus process data word to pass over fieldbus.
P20.1.2 1557 FB Data Output 2 Sel 1,2, 3, 4 RW
Selects fieldbus process data word to pass over fieldbus.
P20.1.3 1558 FB Data Output 3 Sel 1,2, 3, 4 RW
Selects fieldbus process data word to pass over fieldbus.
P20.1.4 1559 FB Data Output 4 Sel 1,2, 3, 4 RW
Selects fieldbus process data word to pass over fieldbus.
P20.1.5 1560 FB Data Output 5 Sel 1,2, 3, 4 RW
Selects fieldbus process data word to pass over fieldbus.
P20.1.6 1561 FB Data Output 6 Sel 1,2, 3, 4 RW
Selects fieldbus process data word to pass over fieldbus.
P20.1.7 1562 FB Data Output 7 Sel 1,2, 3, 4 RW
Selects fieldbus process data word to pass over fieldbus.
P20.1.8 1563 FB Data Output 8 Sel 1,2, 3, 4 RW
Selects fieldbus process data word to pass over fieldbus.
P20.2.1 586 RS-485 Comm Set 1, 2, 3, 4 RW
This parameter defines the communication protocol for RS-485.
0 Modbus RTU
1 BACnet MS/TP
P20.2.2 587 Slave Address 1,2, 3, 4 RW
This parameter defines the slave address for RS-485 communication.
P20.2.3 584 Baud Rate 1,2, 3, 4 RW
This parameter defines communication speed for RS-485 communication.
P20.2.4 585 Parity Type 1,2, 3, 4 RW
This parameter defines parity type for RS-485 communication.
Code Modbus ID Parameter Application
RO/RW