PowerXL DG1 Series Adjustable Frequency Drives MN040004EN—March 2014 www.eaton.com 179
P16.5 581 Motor Nom Freq 2 2, 3, 4 RW
The second motor set v
n
. Selected based off of a digital input.
P16.6 1419 Stator Resistor 2 4 RW
The second set of motor stator resistor real value.
P16.7 1420 Rotor Resistor 2 4 RW
The second set of motor rotor resistor real value.
P16.8 1421 Leak Inductance 2 4 RW
The second set of motor leakage inductance real value.
P16.9 1422 Mutual Inductance 2 4 RW
The second set of motor mutual inductance real value.
P16.10 1423 Excitation Current 2 4 RW
The second set of motor no-load current real value.
P17.1 1418 Bypass Enable 2, 3, 4 RW
This parameter identifies whether or not to enter into bypass mode. The “Bypass”
soft key on keypad will show to start bypass.
P17.2 544 Bypass Start Delay 2, 3, 4 RW
This parameter specifies the time delay between when the Start Signal is applied in
I/O or Fieldbus, to when the motor starts.
P17.3 542 Auto Bypass 2, 3, 4 RW
This parameter specifies whether an automatic switch to bypass will occur based on
Overvoltage Fault Auto Bypass P10.5 through Undervoltage Fault Auto Bypass P10.9
parameters below.
0 Auto Bypass disabled
1 Auto Bypass enabled
P17.4 543 Auto Bypass Delay 2, 3, 4 RW
This parameter specifies the time delay before an automatic switch to bypass, as
determined by Overvoltage Fault Auto Bypass P10.5 through Undervoltage Fault
Auto Bypass P10.9 parameters, will occur.
P17.5 547 Overcurrent Bypass Enable 2, 3, 4 RW
This parameter specifies whether an automatic switch to bypass will occur after the
overcurrent fault auto-restart tries have been exceeded.
0 Auto bypass on overcurrent fault tries exceeded disabled, bypass once fault
happens
1 Auto bypass on overcurrent fault tries exceeded enabled, bypass after tries
exceed
P17.6 546 IGBT FLT Bypass Enable 2, 3, 4 RW
This parameter specifies whether an automatic switch to bypass will occur after the
IGBT fault auto-restart tries have been exceeded.
0 Auto bypass on IGBT fault tries exceeded disabled
1 Auto bypass on IGBT fault tries exceeded enabled
P17.7 548 4 mA FLT Bypass Enable 2, 3, 4 RW
This parameter specifies whether an automatic switch to bypass will occur after the
loss of reference fault and auto-restart tries have been exceeded.
0 Auto bypass on loss of reference fault tries exceeded disabled
1 Auto bypass on loss of reference fault tries exceeded enabled
Note: P1.7.1 (4 mA (Reference) Fault Auto Bypass) must be set to 4 or 5 (Fault).
Code Modbus ID Parameter Application
RO/RW