Firmware Manual
Appendix A—Description of Parameters
PowerXL DG1 Series Adjustable Frequency Drives MN040004EN—March 2014 www.eaton.com 175
P12.1 105 Preset Speed 1 1, 2, 3, 4 RW
P12.2 106 Preset Speed 2 1, 2, 3, 4 RW
Parameter values are automatically limited between the minimum and maximum
frequencies (P1.1, P1.2). Sets the desired frequency when input is applied.
P12.3 118 Preset Speed 3 1, 2, 3, 4 RW
P12.4 119 Preset Speed 4 1, 2, 3, 4 RW
P12.5 120 Preset Speed 5 1, 2, 3, 4 RW
P12.6 121 Preset Speed 6 1, 2, 3, 4 RW
P12.7 122 Preset Speed 7 1, 2, 3, 4 RW
These parameter values define the Multi-step speeds selected. These parameter
values are automatically limited between minimum and maximum frequency (P1.1
and P1.2).
P13.1 295 Torque Limit 4 RW
With this parameter you can set the torque limit control between 0.0–400.0%.
P13.2 296 TorqLimCtrl P 4 RW
This parameter defines the gain of the torque limit controller.
P13.3 297 TorqLimCtrl I 4 RW
This parameter determines the I-gain of the torque limit controller.
P13.4 303 Torque Ref Sel 4 RW
Defines the source for torque reference.
0 Not used
1 AI1
2 AI2
3 SlotA:AI1
4 SlotB:AI1
5 AI1 joystick
6 AI2 joystick
7 Keypad Torque Ref
8 Fieldbus Ref
P13.5 782 Keypad Torque Ref 4 RW
Keypad torque reference setpoint.
P13.6 304 Torque Ref Max 4 RW
P13.7 305 Torque Ref Min 4 RW
Scale the custom minimum and maximum levels for analog inputs within –300.0 to
300.0%.
P13.8 300 Torque Ctrl Freq Min 4 RW
Defines the frequency limit below which the frequency converter operates in the
frequency control mode.
Because of the nominal slip of the motor, the internal torque calculation is inaccurate
at low speeds where it is recommended to use the frequency control mode.
P13.9 301 OL Torque Control P 4 RW
Defines the P gain of the torque controller.
P13.10 302 OL Torque Control I 4 RW
Defines the I gain of the torque controller.
Code Modbus ID Parameter Application
RO/RW