Firmware Manual

Appendix A—Description of Parameters
PowerXL DG1 Series Adjustable Frequency Drives MN040004EN—March 2014 www.eaton.com 159
P8.17 1585 Frequency Ramp Out Filter Time Constant 1,2,3,4 RW
Filter time used when ramping the drive to a stop.
P8.18 1591 Speed Error Filter Time Constant 4 RW
Speed control filter time in open loop speed control mode.
P8.19 1592 Speed Error Band Stop Frequency 4 RW
Stop frequency band when in speed control mode.
P8.20 1593 Speed Control Kp 4 RW
Open loop speed control gain.
P8.21 1594 Speed Control Ti 4 RW
Open loop speed control integral time.
P8.22 1595 Speed Control Kp at Field Weakening 4 RW
Open loop speed control gain at Field Weakening Point.
P8.23 1596 Speed Control Kp Below F0 4 RW
Open loop speed control gain below 0 Hz.
P8.24 1597 Speed Control F0 4 RW
Open loop speed control at frequency 0.
P8.25 1598 Speed Control F1 4 RW
Open loop speed control at frequency 1.
P8.26 1599 Speed Control Kp Below T0 4 RW
Open loop speed gain below torque 0.
P8.27 1600 Speed Control T0 4 RW
Open loop speed torque 0.
P8.28 1601 Speed Control Kp Filter Time Constant 4 RW
Open loop speed control gain filter time.
P8.29 1602 Motor Torque lImit 4 RW
Torque limit setting in open loop torque control mode.
P8.30 1603 Generator Torque Limit 4 RW
Torque limit setting for generator.
P8.31 1604 Torque Limit Forward 4 RW
Torque limit setting in forward direction.
P8.32 1605 Torque Limit Reverse 4 RW
Torque limit setting in reverse direction.
P8.33 1607 Motor Power Limit 4 RW
Motor power limit setting in open loop torque control mode.
P8.34 1608 Generator Power Limit 4 RW
Generator power limit setting in open loop torque control mode.
P8.35 1611 Acc Compensation Time Constant 4 RW
Acceleration compensation time.
P8.36 1612 Acc Compensation Filter Time Constant 4 RW
Acceleration compensation filter time.
P8.37 1620 Flux Reference 4 RW
Reference selection for the amount of flux to output to the motor when using
advanced programming.
P8.38 1621 Stop State Magnetization 4 RW
Magnetization current % level when performing advanced programming of motor
identification.
Code Modbus ID Parameter Application
RO/RW