Firmware Manual
Appendix A—Description of Parameters
PowerXL DG1 Series Adjustable Frequency Drives MN040004EN—March 2014 www.eaton.com 153
P7.12 248 Ramp 2 Shape 1, 2, 3, 4 RW
The start and end of the acceleration and deceleration ramps can be smoothed with
these parameters. Setting a value of 0.0 gives a linear ramp shape that causes
acceleration and deceleration to react immediately to the changes in the reference
signal.
Setting a value from 0.1 to 10 seconds for this parameter produces an S-shaped
acceleration/deceleration. The acceleration time is determined with P1.3 and P1.4 or
P7.13 and P7.14.
Figure 53. Acceleration/Deceleration (S-shaped)
P7.13 249 Accel Time 2 1, 2, 3, 4 RW
P7.14 250 Decel Time 2 1, 2, 3, 4 RW
These values correspond to the time required for the output frequency to accelerate
from the zero frequency to the set maximum frequency (P1.2). These parameters
provide the possibility to set two different acceleration/deceleration time sets for
one application. The active set can be selected with the programmable digital input.
P7.15 256 Skip F1 Low Lim 1, 2, 3, 4 RW
P7.16 257 Skip F1 High Lim 1, 2, 3, 4 RW
P7.17 258 Skip F2 Low Lim 1, 2, 3, 4 RW
P7.18 259 Skip F2 High Lim 1, 2, 3, 4 RW
P7.19 260 Skip F3 Low Lim 1, 2, 3, 4 RW
Code Modbus ID Parameter Application
RO/RW
P7.11 (P7.12)
P7.11 (P7.12)
P1.3, P1.4
(P7.13, P7.14)
t
Hz