150 PowerXL DG1 Series Adjustable Frequency Drives MN040004EN—March 2014 www.eaton.com
P5.18 168 Power Limit Supv Val 1, 2, 3, 4 RW
This power value is supervised by P5.17.
If the calculated power value falls below or exceeds the set limit (P5.18), this
function generates a warning message via the digital output DO1 or via a relay
output RO1, RO2 or RO3, depending on the settings of P5.1 to P5.2, P5.3, and P5.4.
P5.19 170 AI Supv Select 1, 2, 3, 4 RW
Selects analog signal to use for the AI supervision.
0 Analog reference from AI1 (terminals 2 and 3, e.g., potentiometer)
1 Analog reference from AI2 (terminals 4 and 5, e.g., transducer)
P5.20 171 AI Limit Supv 1, 2, 3, 4 RW
Selects how the frequency converter functions upon the value setting.
0 No supervision
1 Low limit supervision
2 High limit supervision
P5.21 172 AI Limit Supv Val 1, 2, 3, 4 RW
The value of the selected analog input to be supervised by P5.20.
If the value of the selected analog input goes under/over the set limit (P5.21), this
function generates a warning message through the digital output or the relay outputs
depending on the settings of P5.1 to P5.2, P5.3, and P5.4.
P5.22 1346 PID1 Superv Enable 2, 3, 4 RW
P5.23 1347 PID1 Superv Upper Limit 2, 3, 4 RW
P5.24 1349 PID1 Superv Lower Limit 2, 3, 4 RW
P5.25 1351 PID1 Superv Delay 2, 3, 4 RW
P5.26 1408 PID2 Superv Enable 3, 4 RW
P5.27 1409 PID2 Superv Upper Limit 3, 4 RW
P5.28 1411 PID2 Superv Lower Limit 3, 4 RW
P5.29 1413 PID2 Superv Delay 3, 4 RW
Upper and lower limits around the reference are set. When the actual value goes
above or below these, a counter starts counting up toward the Delay. When the
actual value is within the allowed area, the same counter counts down instead. After
the delay time it will turn on an relay output value.
P5.30 2111 RO1 On Delay 1, 2, 3, 4 RW
Delay time for RO1 to turn on.
P5.31 2112 RO1 Off Delay 1, 2, 3, 4 RW
Delay time for RO1 to turn off.
P5.32 2113 RO2 On Delay 1, 2, 3, 4 RW
Delay time for RO2 to turn on.
P5.33 2114 RO2 Off Delay 1, 2, 3, 4 RW
Delay time for RO2 to turn off.
P5.34 2115 RO3 On Delay 1, 2, 3, 4 RW
Delay time for RO3 to turn on.
P5.35 2116 RO3 Off Delay 1, 2, 3, 4 RW
Delay time for RO3 to turn off.
P5.36 2117 RO3 Reverse 1, 2, 3, 4 RW
Inverts the operation of RO3.
1 Not Inverted
2 Inverted