Firmware Manual
Appendix A—Description of Parameters
146 PowerXL DG1 Series Adjustable Frequency Drives MN040004EN—March 2014 www.eaton.com
P5.4 538 RO3 Function 1, 2, 3, 4 RW
Code Modbus ID Parameter Application
RO/RW
Application Function Standard
Multi-
Pump
and Fan
Multi-
PID
Multi-
Purpose
0 = Not used
1 = Ready
2 = Run
3 = Fault
4 = Fault inverted
5 = Warning
Not operational
Frequency converter is ready for operations
Frequency converter is running motor
A fault trip has occurred on NO contact close
A fault trip has not occurred on NO contact close
Warning exists in frequency converter
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
6 = Reverse
7 = At speed
8 = Zero frequency
9 = Frequency Limit1 supervision
10 = Frequency Limit2 supervision
Reverse command has been activated
Output frequency has reached reference
Motor output is at zero frequency
Frequency limit1 achieved
Frequency limit2 achieved
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
11 = PID1 supervision
12 = PID2 supervision
13 = Over heat warning
14 = Over current regulator
15 = Over voltage regulator
PID1 controller level achieved
PID2 controller level achieved
Drive over heat has occurred
Over current controller activated
Over voltage controller activated
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
16 = Under voltage regulator
17 = 4 mA fault
18 = External brake
19 = External brake inverter
20 = Torque limit supervision
Under voltage controller activated
4 mA reference fault
External brake activated on contact close
External brake non-activate on contact close
Torque limit value achieved
■
■
—
—
■
■
■
—
—
■
■
■
—
—
■
■
■
■
■
■
21 = Reference limit supervision
22 = Control from IO
23 = Unrequired rotation direction
24 = Thermal fault
25 = Fire mode
Reference limit achieved
Control place I/O is activated
Active direction is different than reference direction
Frequency converter thermal fault
Fire mode is activated
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
26 = Bypass running
27 = External fault
28 = Remote control
29 = Jog speed
30 = Motor thermal protection
Bypass mode is activated
External fault input is activated
Remote control place is activated
Jog preset speed mode is activated
Motor calculated temperature fault activated
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
31 = Fieldbus input1
32 = Fieldbus input2
33 = Fieldbus input3
34 = Fieldbus input4
35 = Damper control
—
—
—
—
Damper control input is activated
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
36 = Timer1 status
37 = Timer2 status
38 = Timer3 status
39 = Emergency stop
40 = Power limit supervision
Timer1 activated
Timer2 activated
Timer3 activated
Emergency stop input activated
Power limit value achieved
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
41 = Temperature limit supervision
42 = Analog input supervision
43 = Motor1 control
44 = Motor2 control
45 = Motor3 control
Temperature limit value achieved
Analog limit value achieved
Auxiliary motor1 activated
Auxiliary motor2 activated
Auxiliary motor3 activated
■
■
—
—
—
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
46 = Motor4 control
47 = Motor5 control
48 = Logic fulfilled
49 = PID1 sleep
50 = PID2 sleep
Auxiliary motor4 activated
Auxiliary motor5 activated
Logic function is activated
PID1 controller sleep mode active
PID2 controller sleep mode active
—
—
—
—
—
■
■
—
■
—
■
■
—
■
■
■
■
■
■
■