P3.30 351 PID1 Set Point Sel 2, 3, 4 RW
P3.31 352 PID2 Set Point Sel 3, 4 RW
Selection allows for selecting between Setpoint 1 and Setpoint 2 when in the PID
control mode. Different settings: DigiIN:X indicates on board terminal inputs,
DigiIN:A:IOX:X indicates optional board inputs in A slot, DigiIN:B:IOX:X indicates
optional board inputs in B slot, or Timer Channel X.
Closed contact: setpoint2 is selected for PID1.
Open contact: setpoint1 is selected for PID1.
P3.32 199 Jog Enable 1, 2, 3, 4 RW
Selection enables the jog frequency reference. Different settings: DigiIN:X indicates
on board terminal inputs, DigiIN:A:IOX:X indicates optional board inputs in A slot,
DigiIN:B:IOX:X indicates optional board inputs in B slot, or Timer Channel X.
Closed contact: drive is under jog mode.
P3.33 224 Start Timer 1 2, 3, 4 RW
P3.34 225 Start Timer 2 2, 3, 4 RW
P3.35 226 Start Timer 3 2, 3, 4 RW
Selection enables the timer functions to begin counting. Different settings: DigiIN:X
indicates on board terminal inputs, DigiIN:A:IOX:X indicates optional board inputs in
A slot, DigiIN:B:IOX:X indicates optional board inputs in B slot, or Timer Channel X.
Closed contact: Timer1,Timer2 or Timer3 will be started.
P3.36 208 AI Ref Source Select 1, 2, 3, 4 RW
Selection switches between AI1 and AI2 reference signals. Different settings:
DigiIN:X indicates on board terminal inputs, DigiIN:A:IOX:X indicates optional board
inputs in A slot, DigiIN:B:IOX:X indicates optional board inputs in B slot, or Timer
Channel X.
Closed contact: AI2 is selected for reference source.
Open contact: AI1 is selected for reference source.
P3.37 210 Motor Interlock 1 2, 3, 4 RW
P3.38 211 Motor Interlock 2 2, 3, 4 RW
P3.39 212 Motor Interlock 3 2, 3, 4 RW
P3.40 213 Motor Interlock 4 2, 3, 4 RW
P3.41 214 Motor Interlock 5 2, 3, 4 RW
Selects inputs that are allowed to verify aux motors are connected to allow them to
run. Different settings: DigiIN:X indicates on board terminal inputs, DigiIN:A:IOX:X
indicates optional board inputs in A slot, DigiIN:B:IOX:X indicates optional board
inputs in B slot, or Timer Channel X.
Closed contact: motor interlock signal activated.
Open contact: motor interlock signal unactivated.
P3.42 747 Emergency Stop 1, 2, 3, 4 RW
Function disables the frequency converter from running the motor. Different
settings: DigiIN:X indicates on board terminal inputs, DigiIN:A:IOX:X indicates
optional board inputs in A slot, DigiIN:B:IOX:X indicates optional board inputs in B
slot, or Timer Channel X.
Contact Open: Disables the ability for the motor to Run.
Contact Close: Enables the ability for the motor to Run.
P3.43 1246 BypassOverLoad 2, 3, 4 RW
Function faults frequency converter when using an overload block input. Different
settings: DigiIN:X indicates on board terminal inputs, DigiIN:A:IOX:X indicates
optional board inputs in A slot, DigiIN:B:IOX:X indicates optional board inputs in B
slot, or Timer Channel X.
Closed contact: motor is over load in bypass.
Use TTF method to realize the above functions.
Code Modbus ID Parameter Application