Firmware Manual
Appendix A—Description of Parameters
PowerXL DG1 Series Adjustable Frequency Drives MN040004EN—March 2014 www.eaton.com 141
P3.22 197 Local Control 1, 2, 3, 4 RW
Selection allows for external control panel to control frequency converters control
place. Different settings: DigiIN:X indicates on board terminal inputs, DigiIN:A:IOX:X
indicates optional board inputs in A slot, DigiIN:B:IOX:X indicates optional board
inputs in B slot, or Timer Channel X.
Closed contact: force to local control.
P3.23 209 Remote1/2 Select 1, 2, 3, 4 RW
Selection allows for switching between Remote control 1 and control 2. Different
settings: DigiIN:X indicates on-board terminal inputs, DigiIN:A:IOX:X indicates
optional board inputs in A slot. DigiIN:B:IOX:X indicates optional board inputs in B
slot, or Timer Channel X.
Closed contact: remote2 is selected as control source.
Open contact: remote1 is selected as control.
P3.24 217 Second Motor Para Select 2, 3, 4 RW
Selection allows for switching between motor parameter set 1 and set 2. Different
settings: DigiIN:X indicates on board terminal inputs, DigiIN:A:IOX:X indicates
optional board inputs in A slot, DigiIN:B:IOX:X indicates optional board inputs in B
slot, or Timer Channel X.
Closed contact: the 2nd motor parameters are applied.
P3.25 218 Bypass Start 2, 3, 4 RW
Selection allows for switching between bypass and drive modes. Different settings:
DigiIN:X indicates on board terminal inputs, DigiIN:A:IOX:X indicates optional board
inputs in A slot, DigiIN:B:IOX:X indicates optional board inputs in B slot, or Timer
Channel X.
Closed contact: switch to bypass.
Open contact: switch to drive.
P3.26 202 DC Brake Enable 1, 2, 3, 4 RW
Selection enables DC brake on a closed contact. Different settings: DigiIN:X
indicates on board terminal inputs, DigiIN:A:IOX:X indicates optional board inputs in
A slot, DigiIN:B:IOX:X indicates optional board inputs in B slot, or Timer Channel X.
Closed contact: DC brake function is enabled.
P3.27 219 Smoke Mode 2, 3, 4 RW
Selection enables the smoke purge preset. Different settings: DigiIN:X indicates on
board terminal inputs, DigiIN:A:IOX:X indicates optional board inputs in A slot,
DigiIN:B:IOX:X indicates optional board inputs in B slot, or Timer Channel X.
Closed contact: drive is in smoke purge mode.
P3.28 220 Fire Mode 2, 3, 4 RW
Selection enables drive into fire mode where faults will be ignored and preset
speeds are given for reference. Different settings: DigiIN:X indicates on board
terminal inputs, DigiIN:A:IOX:X indicates optional board inputs in A slot,
DigiIN:B:IOX:X indicates optional board inputs in B slot, or Timer Channel X.
Closed contact: drive is in fire mode. Ignores all the faults.
P3.29 221 Fire Mode Ref Select 2, 3, 4 RW
Selection allows for switching between fire mode speed reference 1 and reference
2. Different settings: DigiIN:X indicates on board terminal inputs, DigiIN:A:IOX:X
indicates optional board inputs in A slot, DigiIN:B:IOX:X indicates optional board
inputs in B slot, or Timer Channel X.
Closed contact: drive output reference frequency selection 2.
Code Modbus ID Parameter Application
RO/RW