Firmware Manual
Appendix A—Description of Parameters
PowerXL DG1 Series Adjustable Frequency Drives MN040004EN—March 2014 www.eaton.com 135
P2.7 178 AI1 Joystick Hyst 1, 2, 3, 4 RW
This parameter defines the joystick hysteresis between 0 and 20%. When the
joystick is turned from reverse to forward, the output frequency falls linearly to the
selected minimum frequency (joystick in middle position) and stays there until the
joystick is turned toward the forward command. How much the joystick must be
turned to start the increase of the frequency toward the selected maximum
frequency is dependent on the amount of joystick hysteresis defined with this
parameter.
If the value of this parameter is 0, the frequency starts to increase linearly
immediately when the joystick is turned toward the forward command from the
middle position. When the control is changed from forward to reverse, the frequency
follows the same pattern the other way around. See Figure 41.
Figure 41. Example of Joystick Hysteresis
In this example, the value of P1.2.9 (Sleep limit) =0.
P2.8 179 AI1 Sleep Limit 1, 2, 3, 4 RW
The frequency converter keeps on output min frequency if the AI signal level falls
below the Sleep limit defined within this parameter. This will allow the output to be
shut off after the sleep delay until converter AI signal level rises again.
Figure 42. Example of Sleep Limit Function
Code Modbus ID Parameter Application
RO/RW
Frequency Reference
Hz
Reference
Scaling Max
P2.22= 70 Hz
Max Freq.
P1.2 = 50 Hz
Min Freq. P1.1 =
Ref. Scaling Min
P2.21 = 0 Hz
P2.3/2.13
= 20%
P2.4/2.14
= 90%
Joystick Hysteresis,
P2.7 = 20%
REVERSE
50%
FORWARD
50%
From Reverse to Forward
From Forward to Reverse
Analog
Input (V/mA)
(0 – 10V/20 mA)
A
B
Frequency Reference
Hz
Reference
Scaling Max
P2.22 = 70 Hz
Max Freq.
P1.2 = 50 Hz
Min Freq. P1.1 =
Ref. Scaling Min
P2.21 = 0 Hz
P2.3/2.13
= 20%
P2.4/2.14
= 90%
REVERSE
50%
FORWARD
50%
From Reverse to Forward
From Forward to Reverse
Analog
Input (V/mA)
(0 – 10V/20 mA)
A
B
Sleep Limit
P2.7/2.18 = 7%
Joystick Hysteresis,
P1.2.8 = 20%
START
START
STOP
STOP