Firmware Manual

Appendix A—Description of Parameters
PowerXL DG1 Series Adjustable Frequency Drives MN040004EN—March 2014 www.eaton.com 131
P1.5 486 Motor Nom Current 1, 2, 3, 4 RW
Motor nominal nameplate full load current. Find this value on the rating plate of the
motor.
Figure 36. Motor Parameters from Ratings Plate
P1.6 489 Motor Nom Speed 1, 2, 3, 4 RW
Motor nominal nameplate base speed. Find this value on the rating plate of the
motor.
P1.7 490 Motor PF 1, 2, 3, 4 RW
Motor nominal nameplate full load power factor. Find this value on the rating plate of
the motor.
P1.8 487 Motor Nom Voltage 1, 2, 3, 4 RW
Motor nominal nameplate base voltage. Find this value on the rating plate of the
motor.
P1.9 488 Motor Nom Frequency 1, 2, 3, 4 RW
Motor nominal nameplate base frequency. Find this value on the rating plate of the
motor. This parameter sets the Field Weakening Point (P8.4) to the same value.
P1.10 140 Local/Remote Select 1, 2, 3, 4 RW
This parameter determines the control source. There are two different places from
which the frequency converter can be controlled: Local, Remote, or it will hold last
place on power cycle.
The active control place can also be changed by pressing the LOC/REM button on
the keypad, using a programed digital input, or this parameter. Local control means
keypad. Remote control can be a remote control panel or communication bus. With
remote there are two different control places, remote1 and remote2, which can be
selected based on a digital input setting. For each control place, the actual control
source is selected with this parameter; a different symbol will appear on the
alphanumeric display.
P1.11 135 Remote1 Control Place 1, 2, 3, 4 RW
Selects where the drive will look for the start command. I/O terminals would be from
the digital hardwired inputs. Fieldbus would be a communication bus. Keypad display
will indicate which mode is selected.
P1.12 1695 Local Control Place 1, 2, 3, 4 RW
Selects where the drive will look for the start command. I/O terminals would be from
the digital hardwired inputs or keypad Start/Stop buttons. Keypad display will
indicate which mode is selected.
Code Modbus ID Parameter Application
RO/RW
1410 min
230/400V 4.0/2.3A
50 Hz
–1
0.75 kW
cos
0.67
P1.8
P1.5
P1.6
P1.9
P1.7