Firmware Manual
Chapter 8—Multi-Purpose Application
PowerXL DG1 Series Adjustable Frequency Drives MN040004EN—March 2014 www.eaton.com 123
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
P11.42
2
PID2 Feedforward 1 Max –200.00 200.00 % 100.00 1404
P11.43
12
PID2 Feedforward 2 Source 0 1405 See P10.40
P11.44
2
PID2 Feedforward 2 Min –200.00 200.00 % 0.00 1406
P11.45
2
PID2 Feedforward 2 Max –200.00 200.00 % 100.00 1407
P11.46
2
PID2 Set Point1 Comp
Enable
0 1414 0 = Disabled
1 = Enabled
P11.47
2
PID2 Set Point1 Comp Max –200.00 200.00 % 0.00 1415
P11.48
2
PID2 Set Point 2 Comp
Enable
0 1416 0 = Disabled
1 = Enabled
P11.49
2
PID2 Set Point 2 Comp Max –200.00 200.00 % 0.00 1417
Table 104. Preset Speed—P12
Code Parameter Min. Max. Unit Default ID Note
P12.1
2
Preset Speed 1 0.00 Par. P1.2 Hz 5.00 105
P12.2
2
Preset Speed 2 0.00 Par. P1.2 Hz 10.00 106
P12.3
2
Preset Speed 3 0.00 Par. P1.2 Hz 15.00 118
P12.4
2
Preset Speed 4 0.00 Par. P1.2 Hz 20.00 119
P12.5
2
Preset Speed 5 0.00 Par. P1.2 Hz 25.00 120
P12.6
2
Preset Speed 6 0.00 Par. P1.2 Hz 30.00 121
P12.7
2
Preset Speed 7 0.00 Par. P1.2 Hz 35.00 122
Table 105. Torque Control—P13
Code Parameter Min. Max. Unit Default ID Note
P13.1
2
Torque Limit 0.0 400.0 % 400.0 295
P13.2
2
Torque Limit Control P 0.00 320.00 30.00 296
P13.3
2
Torque Limit Control I 0.00 320.00 2.00 297
P13.4
2
Torque Ref Select 0 303 0 = Not Used
1 = AI1
2 = AI2
3 = Slot A: AI1
4 = Slot B: AI1
5 = AI1 Joystick
6 = AI2 Joystick
7 = Keypad Torque Ref
8 = FB Data Input 1
P13.5 Keypad Torque Ref –300.0 300.0 % 0.0 782
P13.6
2
Torque Ref Max –300.0 300.0 % 100.0 304
P13.7
2
Torque Ref Min –300.0 300.0 % 0.0 305
P13.8
2
Torque Control Freq Min 0.00 Par. P1.2 Hz 3.00 300
P13.9
2
OL Torque Control P 0.00 320.00 1.50 301
P13.10
2
OL Torque Control I 0.00 320.00 1.00 302
P13.11
2
Torque Control Freq Max 0 1666 0 = Max Frequency
1 = Selected Freq. Ref
2 = Preset Speed 7
P13.12
2
Window Pos Width 0.00 50.00 Hz 2.00 1636
P13.13
2
Window Neg Width 0.00 50.00 Hz 2.00 1637
P13.14
2
Window Pos Off Limit 0.00 Par. P13.12 Hz 0.00 1638
Table 103. PID Controller 2—P11, continued
Code Parameter Min. Max. Unit Default ID Note