Firmware Manual
Chapter 8—Multi-Purpose Application
112 PowerXL DG1 Series Adjustable Frequency Drives MN040004EN—March 2014 www.eaton.com
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
P5.7
2
Freq Limit 2 Supv 0 157 0 = No Limit
1 = Low Limit Superv
2 = High Limit Superv
3 = Brake-off Control
4 = Brake-on/off Control
P5.8
2
Freq Limit 2 Supv Val 0.00 Par. P1.2 Hz 0.00 158
P5.9
2
Torque Limit Supv 0 159 0 = No Limit
1 = Low Limit Superv
2 = High Limit Superv
3 = Brake-off Control
P5.10
2
Torque Limit Supv Val –1000.0 1000.0 % 100.0 160
P5.11
2
Ref Limit Supv 0 161 0 = No Limit
1 = Low Limit Superv
2 = High Limit Superv
P5.12
2
Ref Limit Supv Val 0.00 Par. P1.2 Hz 0.00 162
P5.13
2
Ext Brake Off Delay 0.0 100.0 s 0.5 163
P5.14
2
Ext Brake On Delay 0.0 100.0 s 1.5 164
P5.15
2
Temp Limit Supv 0 165 See P5.11
P5.16
2
Temp Limit Supv Val –10.0 75.0 °C 40.0 166
P5.17
2
Power Limit Supv 0 167 See P5.11
P5.18
2
Power Limit Supv Val 0.0 200.0 % 0.0 168
P5.19
2
AI Supv Select 0 170 0 = AI1
1 = AI2
P5.20
2
AI Limit Supv 0 171 See P5.11
P5.21
2
AI Limit Supv Val 0.00 100.00 % 0.00 172
P5.22
2
PID1 Superv Enable 0 1346 0 = Disabled
1 = Enabled
P5.23
2
PID1 Superv Upper Limit Par. P10.5 Par. P10.6 Varies 0.00 1347
P5.24
2
PID1 Superv Lower Limit Par. P10.5 Par. P10.6 Varies 0.00 1349
P5.25
2
PID1 Superv Delay 0 3000 s 0 1351
P5.26
2
PID2 Superv Enable 0 1408 0 = Disabled
1 = Enabled
P5.27
2
PID2 Superv Upper Limit Par. P11.5 Par. P11.6 Varies 0.00 1409
P5.28
2
PID2 Superv Lower Limit Par. P11.5 Par. P11.6 Varies 0.00 1411
P5.29
2
PID2 Superv Delay 0 3000 s 0 1413
P5.30 RO1 On Delay 0 320 s 0 2111
P5.31 RO1 Off Delay 0 320 s 0 2112
P5.32 RO2 On Delay 0 320 s 0 2113
P5.33 RO2 Off Delay 0 320 s 0 2114
P5.34 RO3 On Delay 0 320 s 0 2115
P5.35 RO3 Off Delay 0 320 s 0 2116
P5.36 RO3 Reverse 0 1 0 2117 0 = Not Inverted
1 = Inverted
Table 97. Digital Output—P5, continued
Code Parameter Min. Max. Unit Default ID Note