Firmware Manual
Chapter 7—Multi-PID Application
PowerXL DG1 Series Adjustable Frequency Drives MN040004EN—March 2014 www.eaton.com 97
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
P19.25
2
Interval 5 Channel 0 531 See P19.5
P19.26
2
Timer 1 Duration 0 72000 s 0 511
P19.27
2
Timer 1 Channel 0 532 0 = Not Used
1 = Time Channel 1
2 = Time Channel 2
3 = Time Channel 3
P19.28
2
Timer 2 Duration 0 72000 s 0 513
P19.29
2
Timer 2 Channel 0 533 See P19.27
P19.30
2
Timer 3 Duration 0 72000 s 0 515
P19.31
2
Timer 3 Channel 0 534 See P19.27
Table 82. FB Data Output Sel—P20.1
Code Parameter Min. Max. Unit Default ID Note
P20.1.1
2
FB Data Output 1 Sel 1 1556
P20.1.2
2
FB Data Output 2 Sel 2 1557
P20.1.3
2
FB Data Output 3 Sel 3 1558
P20.1.4
2
FB Data Output 4 Sel 4 1559
P20.1.5
2
FB Data Output 5 Sel 5 1560
P20.1.6
2
FB Data Output 6 Sel 6 1561
P20.1.7
2
FB Data Output 7 Sel 7 1562
P20.1.8
2
FB Data Output 8 Sel 359 1563
Table 83. Modbus RTU—P20.2
Code Parameter Min. Max. Unit Default ID Note
P20.2.1 RS485 Comm Set 0 586 0 = Modbus RTU
1 = BACnet MS/TP
P20.2.2 Slave Address 1 247 18 587
P20.2.3 Baud Rate 2 584 0 = 9600
1 = 19200
2 = 38400
3 = 57600
4 = 115200
P20.2.4 Parity Type 2 585 0 = None
1 = Odd
2 = Even
P20.2.5 Protocol Status 0 588 0 = Initial
1 = Stopped
2 = Operational
3 = Faulted
P20.2.6 Slave Busy 0 589 0 = Not Busy
1 = Busy
P20.2.7 Parity Error 0 590
P20.2.8 Slave Fault 0 591
P20.2.9 Last Fault Response 0 592
P20.2.10 Comm Timeout Modbus RTU ms 2000 593
Table 81. Real Time Clock—P19, continued
Code Parameter Min. Max. Unit Default ID Note