Technical Bulletin
BACnet MS/TP—On-Board Communication
76 PowerXL DG1 Series VFD MN040010EN—May 2014 www.eaton.com
Object Instance Summary
Binary Value Object Instance Summary
The following table summarizes the Binary Value Objects
supported.
Table 98. Binary Value Object Instance Summary
Note: For Present Value Access Types, R = Read-only,
W = Writeable, C = Commandable.
Commandable values support priority arrays and relinquish
defaults.
Instance
ID
Object Name (Related
to Drive Parameter) Description Inactive/Active Text
Preset Value
Access
BV0 Ready State Indicates whether the drive is ready or not Not Ready/Ready R
BV1 Run/Stop State Indicates whether the drive is running or stopped Stop/Run R
BV2 Fwd/Rev State Indicates the rotation direction of motor Fwd/Rev R
BV3 Fault State Indicates if a fault is active OK/Fault R
BV4 Warning State Indicates if a warning is active OK/Warning R
BV5 At Set point Ref. Frequency reached False/True R
BV6 At Zero Speed Motor Running at zero speed False/True R
BV7 Motor Ctrl source Command to change active source for controlling motor LocalMotorCtrl/FBMotorCtrl C
BV8 Speed Reference Source Command to change source of motor speed reference LocalSpeedRef/FBSpeedRef C
BV9 Run/Stop CMD Command to start drive Stop/Run C
BV10 Fwd/Rev CMD Command to change rotational direction Fwd/Rev C
BV11 Reset Fault Command to reset active Fault from drive 0/Reset C
BV12 Digital Input 1 Digital Input 1 OFF/ON R
BV13 Digital Input 2 Digital Input 2 OFF/ON R
BV14 Digital Input 3 Digital Input 3 OFF/ON R
BV15 Digital Input 4 Digital Input 4 OFF/ON R
BV16 Digital Input 5 Digital Input 5 OFF/ON R
BV17 Digital Input 6 Digital Input 6 OFF/ON R
BV18 Digital Input 7 Digital Input 7 OFF/ON R
BV 19 Digital Input 8 Digital Input 8 OFF/ON R
BV 20 Digital Output 1 Digital Output 1 OFF/ON R
BV 21 Digital Output 2 Relay 1 Output OFF/ON R
BV 22 Digital Output 3 Relay 2 Output OFF/ON R
BV 23 Digital Output 4 Relay 3 Output OFF/ON R