Technical Bulletin

BACnet MS/TPOn-Board Communication
74 PowerXL DG1 Series VFD MN040010EN—May 2014 www.eaton.com
BACnet Overview
BACnet Technical Data
Protocol Implementation Conformance Statement (PICS)
Controller Profile
B-ASC
Segmentation Capability
Not supported
Data Link Layer and Routing Options
MS/TP Master Baud rates
(9600,19200,38400, 76800, 115200)
Character Sets Supported
UTF8
BIBBS Supported
Data Sharing
ReadProperty-B
WriteProperty-B
Device Management
Dynamic Device Binding–B
Dynamic Object Binding–B
DeviceCommunicationControl–B
ReinitializeDevice–B
Alarms and Events: Not supported
Schedules: Not supported
Trends: Not supported
Network Management: Not supported
Table 97. Supported Object Types and Properties Summery
Property
Device
Object Type
Analog Value
Object Type
Binary Value
Object Type
Object_Identifier ■■■
Object_Name ■■■
Object_Type ■■■
System_Status ——
Vendor_Name ——
Vendor_Identifier ——
Model_Name ——
Firmware_Revision ——
Application_Software_Version ——
Location
Description ■■■
Protocol_Version ——
Protocol_Revision ——
Protocol_Services_Supported ——
Protocol_Object_Types_supported ——
Object_List ——
Structured_Object_list
Max_Apdu_Length_Accepted ——
Segmentation_Supported ——
Vt_Classes_Supported
Active_Vt_Sessions
Local_Time
Local_Date
Utc_Offset
Daylight_Savings_Status
Apdu_Segment_Timeout