Technical Bulletin
EtherNet/IP On-Board Communications
PowerXL DG1 Series VFD MN040010EN—May 2014 www.eaton.com 67
Assembly Instance 117
Table 93. Instance 117 (Input). EIP Drive Status Length = 34 bytes
1
This is the actual value from the frequency converter. The value is between 0 and 10000. In the
application, the value is scaled in percentage of frequency area between set minimum and maximum
frequency. (0 = 0.00%–0000 = 100.00%).
2
The RPM Speed Actual is the actual speed of the motor. The unit is RPM.
ByteBit 7Bit 6Bit 5Bit 4Bit 3Bit 2Bit 1Bit 0
0 FBStatusWord (Low Byte)
1 FBStatusWord (High Byte)
2 % Speed Actual (Low Byte)
1
3 % Speed Actual (High Byte)
1
4 RPM Speed Actual (Low Byte)
2
5 RPM Speed Actual (High Byte)
2
6 Reserved
7 Reserved
8 Reserved
9 Reserved
10 Reserved
11 Reserved
12 Reserved
13 Reserved
14 Reserved
15 Reserved
16 Reserved
17 Reserved
18 ProcessDataOut1 (LowByte)
19 ProcessDataOut1 (HighByte)
20 ProcessDataOut2 (LowByte)
21 ProcessDataOut2 (HighByte)
22 ProcessDataOut3 (LowByte)
23 ProcessDataOut3 (HighByte)
24 ProcessDataOut4 (LowByte)
25 ProcessDataOut4 (HighByte)
26 ProcessDataOut5 (LowByte)
27 ProcessDataOut5 (HighByte)
28 ProcessDataOut6 (LowByte)
29 ProcessDataOut6 (HighByte)
30 ProcessDataOut7 (LowByte)
31 ProcessDataOut7 (HighByte)
32 ProcessDataOut8 (LowByte)
33 ProcessDataOut8 (HighByte)