Technical Bulletin
EtherNet/IP On-Board Communications
64 PowerXL DG1 Series VFD MN040010EN—May 2014 www.eaton.com
Assembly Instance 101
Table 87. Instance 101 (Output) Length = 8 Bytes
Note: Process data is sent to the drive independently from the NetRef and NetCtrl bits settings.
Assembly Instance 111
Table 88. Instance 111 (Output) Length = 20 Bytes
1
FBFixedControlWord.
2
This is the reference1 to the frequency converter. Used normally as Speed reference. The allowed scaling
is 0...10000. In the application, the value is scaled in percentage of the frequency area between set
minimum and maximum frequency. (0 = 0.00%–10000 = 100.00%).
ByteBit 7Bit 6Bit 5Bit 4Bit 3Bit 2Bit 1Bit 0
0 NetRef NetCtrl FaultReset RunRev RunFwd
1
2 FBSpeed Reference (Low Byte), rpm
3 FBSpeed Reference (High Byte), rpm
4 FBProcessDataIn1 (Low Byte)
5 FBProcessDataIn1 (High Byte)
6 FBProcessDataIn2 (Low Byte)
7 FBProcessDataIn2 (High Byte)
ByteBit 7Bit 6Bit 5Bit 4Bit 3Bit 2Bit 1Bit 0
0 FBFixedControlWord (Low Byte)
1
1 FBFixedControlWord (High Byte)
1
2 FBSpeedReference (Low Byte)
2
3 FBSpeedReference (High Byte)
2
4 ProcessDataIn1 (LowByte)
5 ProcessDataIn1 (HighByte)
6 ProcessDataIn2 (LowByte)
7 ProcessDataIn2 (HighByte)
8 ProcessDataIn3 (LowByte)
9 ProcessDataIn3 (HighByte)
10 ProcessDataIn4 (LowByte)
11 ProcessDataIn4 (HighByte)
12 ProcessDataIn5 (LowByte)
13 ProcessDataIn5 (HighByte)
14 ProcessDataIn6 (LowByte)
15 ProcessDataIn6 (HighByte)
16 ProcessDataIn7 (LowByte)
17 ProcessDataIn7 (HighByte)
18 ProcessDataIn8 (LowByte)
19 ProcessDataIn8 (HighByte)
Bit Description (Value = 0) Description (Value = 1) Default Range
0STOP RUN 00–1
1 Clockwise Counter-clockwise 0 0–1
2 Rising edge of this bit will reset active fault Rising edge of this bit will reset active fault 0 0–1
3–15 Not in use Not in use 0 0