Technical Bulletin

EtherNet/IP On-Board Communications
58 PowerXL DG1 Series VFD MN040010EN—May 2014 www.eaton.com
Control Supervisor Object, Class 0x29
Table 80. Control Supervisor Object
1
For Active Fault code, refer “CIP Fault Code” mentioned in “List of Fault
Codes Supported by PowerXL EtherNet/IP.
Note: When both Run (Run1 & Run2) attributes set, then
no action.
ID Description Data Type Access Rule Default Range
Class Attributes
01h Revision UINT Get 1
02h Max Instance UINT Get 1
03h Number of Instances UINT Get 1
Class Services
0Eh Get_Attribute_Single
Instance Attributes
03h Run1 (RunForward) BOOL Get / Set 0 0–1
04h Run2 (RunReverse) BOOL Get / Set 0 0–1
05h NetCtrl BOOL Get / Set 0 0–1
06h State USINT Get 0 0–7
07h Running1 BOOL Get 0 0–1
08h Running2 BOOL Get 0 0–1
09h Ready BOOL Get 0 0–1
0Ah Faulted0 BOOL Get 0 0–1
0Bh Warning BOOL Get 0 0–1
0Ch FaultRst BOOL Get / Set 0 0–1
0Fh CtrlFromNet BOOL Get 0 0–1
0Dh Active Fault Code
1
UINT Get 0 0–65535
6Ch Comm Idle Action Value BOOL Get / Set 0 0–1
Instance Services
0Eh Get_Attribute_Single
10h Set_Attribute_Single
05h Reset (Type 0)