Technical Bulletin

EtherNet/IP On-Board Communications
PowerXL DG1 Series VFD MN040010EN—May 2014 www.eaton.com 57
Motor Data Object, Class 0x28
Table 79. Motor Data Object
ID Description Data Type Access Rule Remarks/Default Values
Class Attributes
01 Revision UINT Get 1
02 Max Instance UINT Get 3
03 Number of Instances UINT Get 3
Class Services
0Eh Get_Attribute_Single
Instance 1 Attributes
03h Motor Type USINT-V Get Squirrel cage Induction Motor (7)
06h Rated Current UINT Get 126,1,5000
07h Rated Voltage UINT Get 380,180,690
09h Rated Frequency UINT Get 50,30,400
0Ch Pole Count UINT Get 4,1,8
0Fh Base Speed UINT Get 1440,300,20000
Instance 2 Attributes
03h Motor Type USINT-V Get Squirrel cage Induction Motor (7)
06h First Rated Current UINT-NV Get / Set 126,1,5000
07h First Rated Voltage UINT-NV Get / Set 380,180,690
09h First Rated Frequency UINT-NV Get / Set 50,30,400
0Ch Pole Count UINT Get 4,1,8
0Fh First Base Speed UINT-NV Get / Set 1440,300,20000
Instance 3 Attributes
03h Motor Type USINT-V Get Squirrel cage Induction Motor (7)
06h Second Rated Current UINT-NV Get / Set 120,1,5000
07h Second Rated Voltage UINT-NV Get / Set 380,180,690
09h Second Rated
Frequency UINT-NV Get / Set 50,30,400
0Ch Pole Count UINT Get 4,1,8
0Fh Second Base Speed UINT-NV Get / Set 1440,300,20000
Instance Services
0Eh Get_Attribute_Single
10h Set_Attribute_Single