Technical Bulletin

Modbus TCP On-Board Communications
PowerXL DG1 Series VFD MN040010EN—May 2014 www.eaton.com 27
Process Data Out
This register range is normally used to fast monitoring of the
VFD. Process Data Out is located in range ID 2101–2199.
See table below.
Table 54. Fieldbus Basic Output Table
Table 55. Status Word
Information about the status of the device and messages is
indicated in the Status Word. The Status Word is composed
of 16 bits that have the following meanings.
Table 56. Status Word Bit Descriptions
Table 57. Actual Speed
This is the Actual Speed of the motor.
ID Modbus Register Group Range/Type
2101 32101, 42101 FB Status Word Binary coded
2102 32102, 42102 FB General Status Word Binary coded
2103 32103, 42103 FB Actual Speed Hz
2104 32104, 42104 FB Process Data Out 1
2105 32105, 42105 FB Process Data Out 2
2106 32106, 42106 FB Process Data Out 3
2107 32107, 42107 FB Process Data Out 4
2108 32108, 42108 FB Process Data Out 5
2109 32109, 42109 FB Process Data Out 6
2110 32110, 42110 FB Process Data Out 7
2111 32111, 42111 FB Process Data Out 8
15 14 13 12 11 10 9 8
7 6 5 4 3 2 1 0
————————
RUNEN BYS AREF WARN FLT DIR RUN RDY
Bit
Description
Value = 0 Value = 1
0 Not Ready Ready
1 STOP RUN
2 Clockwise Counterclockwise
3 Faulted
4— Warning
5 Ref. frequency not reached Ref. frequency reached
6 Bypass not activated Bypass activated
7 Run disable Run Enable
8 Not in use Not in use
9–15 Not in use Not In use
151413121110987654321 0
MSB——————————————LSB