Quick Start Guide
Step 5—Standard Parameter List
22 PowerXL DG1 Series Adjustable Frequency Drives MN040012EN—March 2014 www.eaton.com
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
Table 19. FB Data Output Sel—P20.1
Code Parameter Min. Max. Unit Default ID Note
P20.1.1
2
FB Data Output 1 Sel 1 1556
P20.1.2
2
FB Data Output 2 Sel 2 1557
P20.1.3
2
FB Data Output 3 Sel 3 1558
P20.1.4
2
FB Data Output 4 Sel 4 1559
P20.1.5
2
FB Data Output 5 Sel 5 1560
P20.1.6
2
FB Data Output 6 Sel 6 1561
P20.1.7
2
FB Data Output 7 Sel 7 1562
P20.1.8
2
FB Data Output 8 Sel 359 1563
Table 20. Modbus RTU/BACnet MS/TP—P20.2
Code Parameter Min. Max. Unit Default ID Note
P20.2.1 RS485 Comm Set 0 586 0 = Modbus RTU
1 = BACnet MS/TP
P20.2.2 Slave Address 1 247 18 587
P20.2.3 Baud Rate 2 584 0 = 9600
1 = 19200
2 = 38400
3 = 76800
4 = 115200
P20.2.4 Parity Type 2 585 0 = None
1 = Odd
2 = Even
P20.2.5 Protocol Status 0 588 0 = Initial
1 = Stopped
2 = Operational
3 = Faulted
P20.2.6 Slave Busy 0 589 0 = Not Busy
1 = Busy
P20.2.7 Parity Error 0 590
P20.2.8 Slave Fault 0 591
P20.2.9 Last Fault Response 0 592
P20.2.10 Comm Timeout Modbus RTU ms 2000 593
P20.2.11 BACnet Baud Rate 2 594 0 = 9600
1 = 19200
2 = 38400
3 = 76800
4 = 115200
P20.2.12 MAC Address 0 127 1 595
P20.2.13 Instance Number 0 4194302 0 596
P20.2.14 Comm Timeout BACnet ms 6000 598
P20.2.15 Protocol Status 0 599 0 = Stopped
1 = Operational
2 = Faulted
P20.2.16 Fault Code 0 600 0 = None
1 = Sole Master
2 = Duplicate MAC ID
3 = Baud rate fault