Quick Start Guide

Step 5Standard Parameter List
16 PowerXL DG1 Series Adjustable Frequency Drives MN040012EN—March 2014 www.eaton.com
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
P3.15
2
Accel/Decel Time Set 0 195 See P3.2
P3.16
2
Accel/Decel Prohibit 0 201 See P3.2
P3.17
2
No Access To Param 0 215 See P3.2
P3.21
2
Remote Control 9 196 See P3.2
P3.22
2
Local Control 0 197 See P3.2
P3.23
2
Remote1/2 Select 0 209 See P3.2
P3.26
2
DC Brake Enable 0 202 See P3.2
P3.32
2
Jog Enable 0 199 See P3.2
P3.36
2
AI Ref Source Select 0 208 See P3.2
P3.42
2
Emergency Stop 8 747 See P3.2
Table 12. Analog Output—P4
Code Parameter Min. Max. Unit Default ID Note
P4.1
2
AO1 Mode 0 227 0 = 0–20 mA
1 = 0–10V
P4.2
2
AO1 Function 1 146 0 = Not Used
1 = Output Frequency
2 = Freq Reference
3 = Motor Speed
4 = Motor Current
5 = Motor Torque (0–Nom)
6 = Motor Power
7 = Motor Voltage
8 = DC-Bus Voltage
19 = AI1
20 = AI2
21 = Output Freq (–2 to +2N)
22 = Motor Torque (–2 to +2N)
23 = Motor Power (–2 to +2N)
24 = PT100 Temperature
P4.3
2
AO1 Minimum 1 149 0 = 0V / 0 mA
1 = 2V / 4 mA
P4.4
2
AO1 Filter Time 0.00 10.00 s 1.00 147
P4.5
2
AO1 Scale 10 1000 % 100 150
P4.6
2
AO1 Inversion 0 148 See P2.6
P4.7
2
AO1 Offset –100.00 100.00 % 0.00 173
P4.8
2
AO2 Mode 0 228 See P4.1
P4.9
2
AO2 Function 4 229 See P4.2
P4.10
2
AO2 Minimum 1 232 See P4.3
P4.11
2
AO2 Filter Time 0.00 10.00 s 1.00 230
P4.12
2
AO2 Scale 10 1000 % 100 233
P4.13
2
AO2 Inversion 0 231 See P2.6
P4.14
2
AO2 Offset –100.00 100.00 % 0.00 234
Table 11. Digital Input—P3, continued
Code Parameter Min. Max. Unit Default ID Note