Firmware Manual
Chapter 7—Multi-PID Application
PowerXL DG1 Series Adjustable Frequency Drives MN040004EN—March 2014 www.eaton.com 85
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
Table 69. Digital Output—P5
Code Parameter Min. Max. Unit Default ID Note
P5.1
2
DO1 Function 1 151 0 = Not Used
1 = Ready
2 = Run
3 = Fault
4 = Fault Invert
5 = Warning
6 = Reversed
7 = At Speed
8 = Zero Frequency
9 = Freq Limit 1 Superv
10 = Freq Limit 2 Superv
11 = PID1 Superv
12 = PID2 Superv
13 = Overheat Warning
14 = Overcurrent Regular
15 = Overvoltage Regular
16 = Undervoltage Regular
17 = 4 mA Ref Fault/Warning
20 = Torq Limit Superv
21 = Ref Limit Superv
22 = Control from I/O
23 = Un-Requested Rotation
Direction
24 = Thermistor Fault Output
25 = Fire Mode
26 = Bypass Run
27 = Ext Fault/Warning
28 = Remote Control
29 = Jog Speed Select
30 = Motor Therm Protection
31 = FB Digital Input 1
32 = FB Digital Input 2
33 = FB Digital Input 3
34 = FB Digital Input 4
35 = Damper Control
36 = TC1 Status
37 = TC2 Status
38 = TC3 Status
39 = In E-Stop
40 = Power Limit Superv
41 = Temp Limit Superv
42 = Analog Input Superv
43 = Motor 1 Control
44 = Motor 2 Control
45 = Motor 3 Control
46 = Motor 4 Control
47 = Motor 5 Control
49 = PID1 Sleep
50 = PID2 Sleep
P5.2
2
RO1 Function 2 152 See P5.1
P5.3
2
RO2 Function 3 153 See P5.1
P5.4
2
RO3 Function 7 538 See P5.1
P5.5
2
Freq Limit 1 Supv 0 154 0 = No Limit
1 = Low Limit Superv
2 = High Limit Superv
P5.6
2
Freq Limit 1 Supv Val 0.00 Par. P1.2 Hz 0.00 155
P5.7
2
Freq Limit 2 Supv 0 157 0 = No Limit
1 = Low Limit Superv
2 = High Limit Superv