Chapter 7—Multi-PID Application
84 PowerXL DG1 Series Adjustable Frequency Drives MN040004EN—March 2014 www.eaton.com
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
Table 68. Analog Output—P4
Code Parameter Min. Max. Unit Default ID Note
P4.1
2
AO1 Mode 0 227 0 = 0–20 mA
1 = 0–10V
P4.2
2
AO1 Function 1 146 0 = Not Used
1 = Output Frequency
2 = Freq Reference
3 = Motor Speed
4 = Motor Current
5 = Motor Torque (0–Nom)
6 = Motor Power
7 = Motor Voltage
8 = DC-Bus Voltage
9 = PID1 Setpoint
10 = PID1 Feedback 1
11 = PID1 Feedback 2
12 = PID1 Control Error Value
13 = PID1 Control Output
14 = PID2 Setpoint
15 = PID2 Feedback 1
16 = PID2 Feedback 2
17 = PID2 Control Error Value
18 = PID2 Control Output
19 = AI1
20 = AI2
21 = Output Freq (–2 to +2N)
22 = Motor Torque (–2 to +2N)
23 = Motor Power (–2 to +2N)
24 = PT100 Temperature
P4.3
2
AO1 Minimum 1 149 0 = 0V / 0 mA
1 = 2V / 4 mA
P4.4
2
AO1 Filter Time 0.00 10.00 s 1.00 147
P4.5
2
AO1 Scale 10 1000 % 100 150
P4.6
2
AO1 Inversion 0 148 See P2.6
P4.7
2
AO1 Offset –100.00 100.00 % 0.00 173
P4.8
2
AO2 Mode 0 228 See P4.1
P4.9
2
AO2 Function 4 229 See P4.2
P4.10
2
AO2 Minimum 1 232 See P4.3
P4.11
2
AO2 Filter Time 0.00 10.00 s 1.00 230
P4.12
2
AO2 Scale 10 1000 % 100 233
P4.13
2
AO2 Inversion 0 231 See P2.6
P4.14
2
AO2 Offset –100.00 100.00 % 0.00 234