Firmware Manual

Chapter 6—Multi-Pump and Fan Control Application
PowerXL DG1 Series Adjustable Frequency Drives MN040004EN—March 2014 www.eaton.com 65
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
Table 46. PID Controller 1—P10
Code Parameter Min. Max. Unit Default ID Note
P10.1
2
PID1 Control Gain 0.00 200.00 % 100.00 1294
P10.2
2
PID1 Control ITime 0.00 600.00 s 1.00 1295
P10.3
2
PID1 Control DTime 0.00 100.00 s 0.00 1296
P10.4
12
PID1 Process Unit 0 1297 0 = %
1 = 1/min
2 = rpm
3 = ppm
4 = pps
5 = l/s
6 = l/min
7 = l/h
8 = kg/s
9 = kg/min
10 = kg/h
11 = m3/s
12 = m3/min
13 = m3/h
14 = m/s
15 = mbar
16 = bar
17 = Pa
18 = kPa
19 = mVS
20 = kW
21 = °C
22 = GPM
23 = gal/s
24 = gal/min
25 = gal/h
26 = lb/s
27 = lb/min
28 = lb/h
29 = CFM
30 = ft3/s
31 = ft3/min
32 = ft3/h
33 = ft/s
34 = in wg
35 = ft wg
36 = PSI
37 = lb/in2
38 = HP
39 = °F
P10.5
2
PID1 Process Unit Min –99999.99 99999.99 Varies 0.00 1298
P10.6
2
PID1 Process Unit Max –99999.99 99999.99 Varies 100.00 1300
P10.7
2
PID1 Process Unit Decimal 0 4 2 1302
P10.8
12
PID1 Error Inversion 0 1303 See P2.6
P10.9
2
PID1 Dead Band 0.00 99999.99 Varies 0.00 1304
P10.10
2
PID1 Dead Band Delay 0.00 320.00 s 0.00 1306
P10.11
2
PID1 Keypad Set Point 1 Par. P10.5 Par. P10.6 Varies 0.00 1307
P10.12
2
PID1 Keypad Set Point 2 Par. P10.5 Par. P10.6 Varies 0.00 1309
P10.13
2
PID1 Ramp Time 0.00 300.00 s 0.00 1311