Firmware Manual

Chapter 6—Multi-Pump and Fan Control Application
62 PowerXL DG1 Series Adjustable Frequency Drives MN040004EN—March 2014 www.eaton.com
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
P7.14
2
Decel Time 2 0.1 3000.0 s 10.0 250
P7.15
2
Skip F1 Low Limit 0.00 Par. P7.16 Hz 0.00 256
P7.16
2
Skip F1 High Limit Par. P7.15 400.00 Hz 0.00 257
P7.17
2
Skip F2 Low Limit 0.00 Par. P7.18 Hz 0.00 258
P7.18
2
Skip F2 High Limit Par. P7.17 400.00 Hz 0.00 259
P7.19
2
Skip F3 Low Limit 0.00 Par. P7.20 Hz 0.00 260
P7.20
2
Skip F3 High Limit Par. P7.19 400.00 Hz 0.00 261
P7.21
2
Prohibit Accel/Decel Ramp 0.1 10.0 1.0 264
P7.22
2
Power Loss Function 0 267 0 = Disabled
1 = Enabled
P7.23
2
Power Loss Time 0.3 5.0 s 2.0 268
P7.24 Currency 0 8 $ 2121 0 = $
1 = GBP
2 = Eur
3 = JPY
4 = Rs
5 = R$
6 = Fr
7 = Kr
P7.25 Energy Cost 0 2122
P7.26 Data Type 0 4 s 0 2123 0 = Cumulative
1 = Daily Avg
2 = Monthly Avg
3 = Yearly Avg
P7.27 Energy Savings Reset 0 1 s 0 2124 0 = No Action
1 = Reset
Table 44. Motor Control—P8
Code Parameter Min. Max. Unit Default ID Note
P8.1
12
Motor Control Mode 0 287 0 = Freq Control
1 = Speed Control
P8.2
1
Current Limit Drive Nom
CT*1/10
Drive Nom
CT*2
A Drive Nom VT 107
P8.3
12
V/Hz Optimization 0 109 0 = Disabled
1 = Enabled
P8.4
12
V/Hz Ratio 0 108 0 = Linear
1 = Squared
2 = Programmable
3 = Linear + Flux Optimization
P8.5
12
Field Weakening Point 8.00 400.00 Hz Field Weakening
Point Freq
289
P8.6
12
Voltage at FWP 10.00 200.00 % 100.00 290
P8.7
12
V/Hz Mid Frequency 0.00 Par. P8.5 Hz V/Hz Curve
Midpoint Freq
291
P8.8
12
V/Hz Mid Voltage 0.00 100.00 % 100.00 292
P8.9
12
Zero Frequency Voltage 0.00 40.00 % 0.00 293
P8.10
2
Switching Frequency Min Switch
Freq
Max Switch
Freq
kHz Default Switching
Freq
288
P8.11
2
Sine Filter Enable 0 1665 0 = Disabled
1 = Enabled
Table 43. Drive Control—P7, continued
Code Parameter Min. Max. Unit Default ID Note