Firmware Manual
Appendix A—Description of Parameters
PowerXL DG1 Series Adjustable Frequency Drives MN040004EN—March 2014 www.eaton.com 189
M14 25 Analog Output 1 1, 2, 3, 4 RO
Analog output 1 measured value supplied from the drive. Can be a current or voltage
output signal.
M15 575 Analog Output 2 1, 2, 3, 4 RO
Analog output 2 measured value supplied from the drive. Can be a current or voltage
output signal.
M16 12 DI1, DI2, DI3 1, 2, 3, 4 RO
Digital input status.
M17 13 DI4, DI5, DI6 1, 2, 3, 4 RO
Digital input status.
M18 576 DI7, DI8 1, 2, 3, 4 RO
Digital input status.
M19 14 DO1 1, 2, 3, 4 RO
Digital output status.
M20 557 RO1, RO2, RO3 1, 2, 3, 4 RO
Relay output status.
M21 558 TC1, TC2, TC3 2, 3, 4 RO
Timer channel status.
M22 559 Interval 1, 2, 3, 4 RO
Time interval 1 status.
M23 560 Interval 2 2, 3, 4 RO
Time interval 2 status.
M24 561 Interval 3 2, 3, 4 RO
Time interval 3 status.
M25 562 Interval 4 2, 3, 4 RO
Time interval 4 status.
M26 563 Interval 5 2, 3, 4 RO
Time interval 5 status.
M27 569 Timer 1 2, 3, 4 RO
Timer 1 value in seconds.
M28 571 Timer 2 2, 3, 4 RO
Timer 2 value in seconds.
M29 573 Timer 3 2, 3, 4 RO
Timer 3 value in seconds.
M30 16 PID1 Set Point 2, 3, 4 RO
PID1 reference value level.
M31 18 PID1 Feedback 2, 3, 4 RO
PID1 actual value feedback level.
M32 20 PID1 Error Value 2, 3, 4 RO
PID1 difference between set point and feedback value levels.
M33 22 PID1 Output 2, 3, 4 RO
PID1 output percentage to the motor.
M34 23 PID1 Status 2, 3, 4 RO
PID1 status indication. Indicates if drive is stopped, running in PID mode, or in
PID sleep mode.
M35 32 PID2 Set Point 3, 4 RO
PID2 reference value level.
Code Modbus ID Parameter Application
RO/RW