Appendix A—Description of Parameters
184 PowerXL DG1 Series Adjustable Frequency Drives MN040004EN—March 2014 www.eaton.com
P20.2.5 588 Protocol Status 1, 2, 3, 4 RO
This parameter shows the protocol status for RS-485 communication.
0 Initial
1 Stopped
2 Operational
3 Faulted
P20.2.6 589 Slave Busy 1, 2, 3, 4 RO
Shows the status of the Slave device on the network.
P20.2.7 590 Parity Error 1, 2, 3, 4 RO
Counts the amount of Parity Errors seen on the RS-485 network.
P20.2.8 591 Slave Fault 1, 2, 3, 4 RO
Error response given when slave receives message without communication error,
but can't handle it.
P20.2.9 592 Last Fault Response 1, 2, 3, 4 RO
Stores the last active fault for viewing over communications.
P20.2.10 593 Comm Timeout Modbus RTU 1, 2, 3, 4 RW
Selects the time it waits before a communication fault occurs over Modbus RTU if a
message isn't received.
P20.2.11 594 BACnet Baud Rate 1, 2, 3, 4 RW
Communication speed of BACnet.
P20.2.12 595 MAC Address 1, 2, 3, 4 RW
Selects the BACnet Address that the drive will be located at on Instance node.
P20.2.13 596 Instance Number 1, 2, 3, 4 RW
Selects the BACnet Instance value.
P20.2.14 598 Comm Timeout BACnet 1, 2, 3, 4 RW
Selects the time it waits before a communication fault occurs over BACnet.
P20.2.15 599 BACnet Protocol Status 1, 2, 3, 4 RW
Shows the status of the BACnet protocol.
P20.2.16 600 BACnet Fault Code 1, 2, 3, 4 RW
BACnet protocol faults.
0 None
1 Sole Master
P20.3.1 1500 IP Address Mode 1, 2, 3, 4 RW
This parameter defined the IP address configuration mode for EIP/Modbus TCP.
0 DHCP with AutoIP
1 Static IP
P20.3.2 1507 Active IP Address 1, 2, 3, 4 RO
The current used IP address.
P20.3.3 1509 Active Subnet Mask 1, 2, 3, 4 RO
The current used subnet mask.
P20.3.4 1511 Active Default Gateway 1, 2, 3, 4 RO
The current used default gateway.
P20.3.5 1513 MAC Address 1, 2, 3, 4 RO
48 bit hardware address.
P20.3.6 1501 Static IP Address 1, 2, 3, 4 RW
The static IP address. This parameter is used for user to configure the IP address,
when P20.3.1 is set to be 1.
Code Modbus ID Parameter Application
RO/RW