Appendix A—Description of Parameters
PowerXL DG1 Series Adjustable Frequency Drives MN040004EN—March 2014 www.eaton.com 151
P6.1 751 Logic Function Select 4 RW
The logic function enables you to link both parameters P6.2(A) and P6.3 (B) logically
with each other. The result (LOG) can then be assigned to the digital outputs DO,
RO1, RO2 and RO3. The type of operation is defined in parameter P6.1:
0 AND
1 OR
2 XOR
P6.2 752 Logic Operation Input A 4 RW
Input A for Logic function calculation defined in P6.1.
P6.3 753 Logic Operation Input B 4 RW
Input B for Logic function calculation defined in P6.1.
P7.1 138 Remote 2 Control Place 1, 2, 3, 4 RW
Selects where the drive will look for the 2nd start command. I/O terminals would be
from the Digital hardwired inputs. Fieldbus would be a communication bus. Keypad
will indicate what mode is selected. Digital input will select between control place 1
and control place 2.
P7.2 139 Remote 2 Reference 1, 2, 3, 4 RW
Selects what frequency reference source to look at when in the Remote 2 control
mode.
P7.3 141 Keypad Reference 1, 2, 3, 4 RW
The frequency reference can be adjusted from the keypad with this parameter. This
parameter is linked to R1.12 Keypad reference in the operate menu.
P7.4 116 Keypad Direction 1, 2, 3, 4 RW
0 Forward: The rotation of the motor is forward when the keypad is the active
control place.
1 Reverse: The rotation of the motor is reversed when the keypad is the active
control place.
P7.5 114 Keypad Stop 1, 2, 3, 4 RW
To make the STOP button a “hotspot” that always stops the drive regardless of the
selected control place. Set the value of this parameter to Always Enabled for being
used in local and remote. Enable - Keypad operation activates the stop button only in
keypad mode.
Code Modbus ID Parameter Application
RO/RW
Application—Selection Standard
Multi-
Pump
and Fan
Multi-
PID
Multi-
Purpose
0 = AI1—analog input on terminals 2–3
1 = AI2—analog input on terminals 4–5
2 = Slot A: AI1—analog input on expander board in slot A
3 = Slot B: AI1—analog input on expander board in slot B
4 = AI1 joystick—analog input on terminals 2–3, used for joystick control
5 = AI2 joystick—analog input on terminals 4–5, used for joystick control
6 = Keypad—keypad reference (P1.7.3)
7 = Fieldbus Ref—reference sent of communication bus
8 = Motor Pot—selects digital inputs for digital inputs to increase/decrease speed
9 = Max Frequency—maximum frequency value (P1.1.2)
10 = AI1+AI2—sums the analog input values
11 = AI1–AI2—subtracts the analog inputs AI1 from AI2
12 = AI2–AI1—subtracts the analog inputs AI2 from AI1
13 = AI1*AI2—multiplies analog inputs AI1 and AI2
14 = AI1 or AI2—selects analog inputs based off of digital input
15 = Min (AI1, AI2)—selects analog inputs that have the least value
16 = Max (AI1, AI2)—selects analog inputs that have the higher value
17 = PID1 Control—selects the PID calculation for output to maintain reference value