Firmware Manual
Appendix A—Description of Parameters
PowerXL DG1 Series Adjustable Frequency Drives MN040004EN—March 2014 www.eaton.com 147
P5.4 538 RO3 Function, continued 1, 2, 3, 4 RW
Code Modbus ID Parameter Application
RO/RW
Setting Value Signal Content Standard
Multi-
Pump
and Fan
Multi-
PID
Multi-
Purpose
0 = Not used
1 = Ready
2 = Run
3 = Fault
4 = Fault inverted
5 = Warning
Out of operation
Frequency converter is ready for operation
Frequency converter is operating (motor is running)
A fault trip has occurred
A fault trip has not occurred
Always if a warning exists
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
6 = Reverse
7 = At speed
8 = Zero frequency
9 = Frequency Limit1 supervision
10 = Frequency Limit2 supervision
The reverse command has been selected
The output frequency has reached the set
reference
Motor output is at zero frequency
Supervision for frequency limit1
Supervision for frequency limit2
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
11 = PID1 supervision
12 = PID2 supervision
13 = Over heat warning
14 = Over current regulator
15 = Over volt regulator
Supervision for PID1 controller
Supervision for PID2 controller
Drive over heat has occurred
Over current regular is enabled
Over volt regular is enabled
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
16 = Under volt regulator
17 = 4 mA fault
18 = External brake
19 = External brake inverter
20 = Torque limit supervision
Under volt regular is enabled
4 mA fault has occurred
External brake is working
External brake isn’t working
Supervision for torque limit
■
■
—
—
■
■
■
—
—
■
■
■
—
—
■
■
■
■
■
■
21 = Reference limit supervision
22 = Control from IO
23 = Unrequired rotation direction
24 = Thermal fault
25 = Fire mode
Supervision for reference limit
I/O is the control place
The active direction isn’t the same with the
reference direction
Thermal fault has occurred
Drive is in fire mode
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
26 = Bypass running
27 = External fault
28 = Remote control
29 = Jog speed
30 = Motor thermal protection
Drive is in bypass mode
External fault has occurred
Remote is the control place
Drive is in jog mode
Motor is thermal protected
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
31 = Fieldbus input1
32 = Fieldbus input2
33 = Fieldbus input3
34 = Fieldbus input4
35 = Damper control
—
—
—
—
Drive is in damper control
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
36 = Timer1 status
37 = Timer2 status
38 = Timer3 status
39 = Emergency stop
40 = Power limit supervision
The status of timer1
The status of timer2
The status of timer3
Emergency stop has occurred
Supervision for power limit
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
41 = Temperature limit supervision
42 = Analog input supervision
43 = Motor1 control
44 = Motor2 control
45 = Motor3 control
Supervision for temperature limit
Supervision for analog input
Motor1 is controlled
Motor2 is controlled
Motor3 is controlled
■
■
—
—
—
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
46 = Motor4 control
47 = Motor5 control
48 = Logic fulfilled
49 = PID1 sleep
50 = PID2 sleep
Motor4 is controlled
Motor5 is controlled
The status of logic function
PID1 controller is in sleep mode
PID2 controller is in sleep mode
—
—
—
—
—
■
■
—
■
—
■
■
—
■
■
■
■
■
■
■