Firmware Manual

Chapter 8—Multi-Purpose Application
124 PowerXL DG1 Series Adjustable Frequency Drives MN040004EN—March 2014 www.eaton.com
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
P13.15
2
WindowNeg Off Limit 0.00 Par. P13.13 Hz 0.00 1639
P13.16
2
Torque Reference Filter TC 0 32000 ms 0 1640
P13.17 Pull Out Torque 0 1000.0 % 250.0 1606
P13.18 Startup Torque Time 0 10000 ms 50 1667
P13.19 Stop State Magnetization
Time
0 32000 S 0 1684
Table 106. Brake—P14
Code Parameter Min. Max. Unit Default ID Note
P14.1
12
DC-Brake Current Drive Nom
CT*15/100
Drive Nom
CT*15/10
A Drive Nom CT*1/2 254
P14.2
12
Start DC-Brake Time 0.00 600.00 s 0.00 263
P14.3
12
Stop DC-Brake Frequency 0.10 10.00 Hz 1.50 262
P14.4
12
Stop DC-Brake Time 0.00 600.00 s 0.00 255
P14.5
12
Brake Chopper 0 251 0 = Disabled
1 = B(Run) T(Rdy)
2 = External
3 = B(Rdy) T(Rdy)
4 = B(Run) T(No)
P14.6
12
Flux Brake 0 266 0 = Off
1 = On
P14.7
12
Flux Brake Current Active Motor
Nom I*1/10
Par. P8.2 A Active Motor Nom
I*1/2
265
Table 107. Fire Mode—P15
Code Parameter Min. Max. Unit Default ID Note
P15.1
12
Fire Mode Function 0 535 0 = Closing Contact
1 = Opening Contact
P15.2
12
Fire Mode Ref Select
Function
0 536 0 = Disabled
1 = Enabled
P15.3
2
Fire Mode Min Frequency Par. P1.1 Par. P1.2 Hz 15.00 537
P15.4
2
Fire Mode Freq Ref 1 0.0 100.0 % 75.0 565
P15.5
2
Fire Mode Freq Ref 2 0.0 100.0 % 100.0 564
P15.6
12
Smoke Purge Frequency 0.0 100.0 % 50.0 554
Table 108. Second Motor Parameter—P16
Code Parameter Min. Max. Unit Default ID Note
P16.1
1
Motor Nom Current 2 Drive Nom
CT*1/10
Drive Nom
CT*2
A Drive Nom CT 577
P16.2
1
Motor Nom Speed 2 300 20000 rpm 2nd Motor Nom
Speed
578
P16.3
1
Motor PF 2 0.30 1.00 0.85 579
P16.4
1
Motor Nom Volt 2 180 690 V 2nd Motor Nom Volt 580
P16.5
1
Motor Nom Freq 2 8.00 400.00 Hz 2nd Motor Nom Freq 581
P16.6
1
Stator Resistor 2 0.001 65.535 ohm 0.033 1419
P16.7
1
Rotor Resistor 2 0.001 65.535 ohm 0.034 1420
Table 105. Torque Control—P13, continued