Firmware Manual
Chapter 8—Multi-Purpose Application
116 PowerXL DG1 Series Adjustable Frequency Drives MN040004EN—March 2014 www.eaton.com
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
P8.4
12
V/Hz Ratio 0 108 0 = Linear
1 = Squared
2 = Programmable
3 = Linear + Flux Optimization
P8.5
12
Field Weakening Point 8.00 400.00 Hz Field Weakening
Point Freq
289
P8.6
12
Voltage at FWP 10.00 200.00 % 100.00 290
P8.7
12
V/Hz Mid Frequency 0.00 Par. P8.5 Hz V/Hz Curve
Midpoint Freq
291
P8.8
12
V/Hz Mid Voltage 0.00 100.00 % 100.00 292
P8.9
12
Zero Frequency Voltage 0.00 40.00 % 0.00 293
P8.10
2
Switching Frequency Min Switching
Freq
Max Switching
Freq
kHz Default Switching
Freq
288
P8.11
2
Sine Filter Enable 0 1665 0 = Disabled
1 = Enabled
P8.12
12
Overvoltage Control 1 294 0 = Disabled
1 = Enabled
P8.13
2
Load Drooping 0.00 100.00 % 0.00 298
P8.14
2
Identification 0 299 0 = No Action
1 = Identification Only Stator
Resistor
2 = Identification with Run
3 = Identification No Run
P8.15
12
Neg Frequency Limit –400.00 Par. P8.16 Hz –400.00 1574
P8.16
12
Pos Frequency Limit Par. P8.15 400.00 Hz 400.00 1576
P8.17
2
Frequency Ramp Out
FilterTime Constant
0 3000 ms 0 1585
P8.18
2
Speed Error Filter Time
Constant
0 3000 ms 0 1591
P8.19
2
Speed Error Band Stop
Frequency
0.00 320.00 Hz 0.00 1592
P8.20
2
Speed Control Kp 0.0 1000.0 % 30.0 1593
P8.21
2
Speed Control Ti 0.0 3200.0 ms 20.0 1594
P8.22
2
Speed Control Kp At Field
Weakening
0.0 1000.0 % 100.0 1595
P8.23
2
Speed Control Kp Below F0 0.0 1000.0 % 0.0 1596
P8.24
2
Speed Control F0 0.00 Par. P8.25 Hz 0.00 1597
P8.25
2
Speed Control F1 Par. P8.24 Par. P8.5 Hz 0.00 1598
P8.26
2
Speed Control Kp Below T0 0.0 1000.0 % 0.0 1599
P8.27
2
Speed Control T0 0.0 100.0 % 0.0 1600
P8.28
2
Speed Control Kp Filter Time
Constant
0 3000 ms 0 1601
P8.29
2
Motoring Torque Limit 0.0 300.0 % 300.0 1602
P8.30
2
Generator Torque Limit 0.0 300.0 % 300.0 1603
P8.31
2
Torque Limit Forward 0.0 300.0 % 300.0 1604
P8.32
2
Torque Limit Reverse 0.0 300.0 % 300.0 1605
P8.33
2
Motoring Power Limit 0.0 300.0 % 300.0 1607
P8.34
2
Generator Power Limit 0.0 300.0 % 300.0 1608
Table 100. Motor Control—P8, continued
Code Parameter Min. Max. Unit Default ID Note