Firmware Manual
Chapter 7—Multi-PID Application
PowerXL DG1 Series Adjustable Frequency Drives MN040004EN—March 2014 www.eaton.com 99
Table 86. Basic Setting—P21.1
Code Parameter Min. Max. Unit Default ID Note
P21.1.1 Language 0 340 0 = English
1 = English
2 = English
P21.1.2
1
Application 0 142 0 = Standard
1 = Multi-Pump
2 = Multi-PID
3 = Multi-Purpose
P21.1.3 Parameter Sets 0 619 0 = No
1 = Reload Defaults
2 = Reload Set 1
3 = Reload Set 2
4 = Store Set 1
5 = Store Set 2
6 = Reset
P21.1.4 Up To Keypad 0 620 See P21.3.1
P21.1.5 Down From Keypad 0 621 0 = No
1 = All Parameters
2 = All, No Motor
3 = App Parameters
P21.1.6 Parameter Comparison 0 623 0 = No
1 = Compare with Keypad
2 = Compare with Default
3 = Compare with Set 1
4 = Compare with Set 2
P21.1.7 Password 0 9999 0 624
P21.1.8 Parameter Lock 0 625 0 = Change Enable
1 = Change Disable
P21.1.9 Multimonitor Set 0 627 See P21.1.8
P21.1.10 Default Page 0 628 0 = None
1 = Main Menu
2 = Multi-Monitor
P21.1.11 Timeout Time 0 65535 s 30 629
P21.1.12 Contrast Adjust 5 18 12 630
P21.1.13 Backlight Time 0 65535 min 10 631
P21.1.14 Fan Control 3 632 0 = Continuous
1 = Temperature
2 = Run Follow
3 = Calculate Temp
P21.1.15 HMI ACK Timeout 200 5000 ms 200 633
P21.1.16 HMI Retry Number 1 10 5 634
Table 87. Version Info—P21.2
Code Parameter Min. Max. Unit Default ID Note
P21.2.1 Keypad Software Version 640
P21.2.2 Motor Control Software
Version
642
P21.2.3 Application Software
Version
App Firmware 644