Firmware Manual
Chapter 7—Multi-PID Application
PowerXL DG1 Series Adjustable Frequency Drives MN040004EN—March 2014 www.eaton.com 95
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
Table 77. Fire Mode—P15
Code Parameter Min. Max. Unit Default ID Note
P15.1
12
Fire Mode Function 0 535 0 = Closing Contact
1 = Opening Contact
P15.2
12
Fire Mode Ref Select
Function
0 536 0 = Disabled
1 = Enabled
P15.3
2
Fire Mode Min Frequency Par. P1.1 Par. P1.2 Hz 15.00 537
P15.4
2
Fire Mode Freq Ref 1 0.0 100.0 % 75.0 565
P15.5
2
Fire Mode Freq Ref 2 0.0 100.0 % 100.0 564
P15.6
12
Smoke Purge Frequency 0.0 100.0 % 50.0 554
Table 78. Second Motor Parameter—P16
Code Parameter Min. Max. Unit Default ID Note
P16.1
1
Motor Nom Current 2 Drive Nom
CT*1/10
Drive Nom
CT*2
A Drive Nom CT 577
P16.2
1
Motor Nom Speed 2 300 20000 rpm 2nd Motor Nom
Speed
578
P16.3
1
Motor PF 2 0.30 1.00 0.85 579
P16.4
1
Motor Nom Volt 2 180 690 V 2nd Motor Nom Volt 580
P16.5
1
Motor Nom Freq 2 8.00 400.00 Hz 2nd Motor Nom Freq 581
Table 79. Bypass—P17
Code Parameter Min. Max. Unit Default ID Note
P17.1
12
Bypass Enable 0 1418 0 = Disabled
1 = Enabled
P17.2
12
Bypass Start Delay 1 32765 s 5 544
P17.3
12
Auto Bypass 0 542 0 = Disabled
1 = Enabled
P17.4
12
Auto Bypass Delay 0 32765 s 10 543
P17.5
12
Overcurrent Bypass Enable 0 547 0 = Disabled
1 = Enabled
P17.6
12
IGBT Fault Bypass Enable 0 546 0 = Disabled
1 = Enabled
P17.7
12
4 mA Fault Bypass Enable 0 548 0 = Disabled
1 = Enabled
P17.8
12
Undervoltage Bypass Enable 0 545 0 = Disabled
1 = Enabled
P17.9
12
Overvoltage Bypass Enable 0 549 0 = Disabled
1 = Enabled
Table 80. Multi-Pump Control—P18
Code Parameter Min. Max. Unit Default ID Note
P18.1
12
Number of Motors 1 5 1 342
P18.2
2
Bandwidth 0.0 100.0 % 10.0 343
P18.3
2
Bandwidth Delay 0 3600 s 10 344
P18.4
2
Interlock Enable 1 350 0 = Disabled
1 = Enabled
P18.5
2
Include Freq Converter 1 346 0 = Disabled
1 = Enabled