Firmware Manual

Chapter 7—Multi-PID Application
94 PowerXL DG1 Series Adjustable Frequency Drives MN040004EN—March 2014 www.eaton.com
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
P11.42
2
PID2 Feedforward 1 Max –200.00 200.00 % 100.00 1404
P11.43
12
PID2 Feedforward 2 Source 0 1405 See P10.40
P11.44
2
PID2 Feedforward 2 Min –200.00 200.00 % 0.00 1406
P11.45
2
PID2 Feedforward 2 Max –200.00 200.00 % 100.00 1407
P11.46
2
PID2 Set Point1 Comp
Enable
0 1414 0 = Disabled
1 = Enabled
P11.47
2
PID2 Set Point1 Comp Max –200.00 200.00 % 0.00 1415
P11.48
2
PID2 Set Point 2 Comp
Enable
0 1416 0 = Disabled
1 = Enabled
P11.49
2
PID2 Set Point 2 Comp Max –200.00 200.00 % 0.00 1417
Table 75. Preset Speed—P12
Code Parameter Min. Max. Unit Default ID Note
P12.1
2
Preset Speed 1 0.00 Par. P1.2 Hz 5.00 105
P12.2
2
Preset Speed 2 0.00 Par. P1.2 Hz 10.00 106
P12.3
2
Preset Speed 3 0.00 Par. P1.2 Hz 15.00 118
P12.4
2
Preset Speed 4 0.00 Par. P1.2 Hz 20.00 119
P12.5
2
Preset Speed 5 0.00 Par. P1.2 Hz 25.00 120
P12.6
2
Preset Speed 6 0.00 Par. P1.2 Hz 30.00 121
P12.7
2
Preset Speed 7 0.00 Par. P1.2 Hz 35.00 122
Table 76. Brake—P14
Code Parameter Min. Max. Unit Default ID Note
P14.1
12
DC-Brake Current Drive Nom
CT*15/100
Drive Nom
CT*15/10
A Drive Nom CT*1/2 254
P14.2
12
Start DC-Brake Time 0.00 600.00 s 0.00 263
P14.3
12
Stop DC-Brake Frequency 0.10 10.00 Hz 1.50 262
P14.4
12
Stop DC-Brake Time 0.00 600.00 s 0.00 255
P14.5
12
Brake Chopper 0 251 0 = Disabled
1 = B(Run) T(Rdy)
2 = External
3 = B(Rdy) T(Rdy)
4 = B(Run) T(No)
P14.6
12
Flux Brake 0 266 0 = Off
1 = On
P14.7
12
Flux Brake Current Active Motor
Nom I*1/10
Par. P8.2 A Active Motor Nom
I*1/2
265
Table 74. PID Controller 2—P11, continued
Code Parameter Min. Max. Unit Default ID Note