1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
P9.21
12
Fieldbus Fault Response 2 334 See P9.11
P9.22
12
OPTCard Fault Response 2 335 See P9.11
P9.23
12
Unit Under Temp Prot 2 1564 See P9.11
P9.24
2
Wait Time 0.10 10.00 s 0.50 321
P9.25
2
Trail Time 0.00 60.00 s 30.00 322
P9.26
2
Start Function 0 323 0 = Ramp
1 = Flying Start
2 = Start
P9.27
2
Undervoltage Attempts 0 10 1 324
P9.28
2
Overvoltage Attempts 0 10 1 325
P9.29
2
Overcurrent Attempts 0 3 1 326
P9.30
2
4 mA Fault Attempts 0 10 1 327
P9.31
2
Motor Temp Fault Attempts 0 10 1 329
P9.32
2
External Fault Attempts 0 10 0 328
P9.33
2
Underload Attempts 0 10 1 336
P9.34
12
RTC Fault 1 955 See P9.11
P9.35
12
PT100 Fault Response 2 337 See P9.11
P9.36
12
Replace Battery Fault
Response
1 1256 See P9.11
P9.37
12
Replace Fan Fault Response 1 1257 See P9.11
P9.38
12
IP Address Confliction Resp 1 1678 See P9.11
P9.39 Cold Weather Mode 0 1 0 2126 0 = No
1 = Yes
P9.40 Cold Weather Voltage Level 0 20 % 2 2127
P9.41 Cold Weather Time Out 0 10 min 3 2128
P9.42 Cold Weather Password 2129
P9.43 Under Temp Fault Override 0 1 0 2130 0 = No
1 = Yes
Table 73. PID Controller 1—P10
Code Parameter Min. Max. Unit Default ID Note
P10.1
2
PID1 Control Gain 0.00 200.00 % 100.00 1294
P10.2
2
PID1 Control ITime 0.00 600.00 s 1.00 1295
P10.3
2
PID1 Control DTime 0.00 100.00 s 0.00 1296
Table 72. Protections—P9, continued
Code Parameter Min. Max. Unit Default ID Note