Firmware Manual

Chapter 7—Multi-PID Application
88 PowerXL DG1 Series Adjustable Frequency Drives MN040004EN—March 2014 www.eaton.com
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
P8.7
12
V/Hz Mid Frequency 0.00 Par. P8.5 Hz V/Hz Curve
Midpoint Freq
291
P8.8
12
V/Hz Mid Voltage 0.00 100.00 % 100.00 292
P8.9
12
Zero Frequency Voltage 0.00 40.00 % 0.00 293
P8.10
2
Switching Frequency Min Switching
Freq
Max Switching
Freq
kHz Default Switching
Freq
288
P8.11
2
Sine Filter Enable 0 1665 0 = Disabled
1 = Enabled
P8.12
12
Overvoltage Control 1 294 0 = Disabled
1 = Enabled
P8.17
2
Frequency Ramp Out
FilterTime Constant
0 3000 ms 0 1585
P8.39
2
Start Boost Rise Time -1 32000 s 0 1622
Table 72. Protections—P9
Code Parameter Min. Max. Unit Default ID Note
P9.1
12
4 mA Input Fault 0 306 0 = No Action
1 = Warning
2 = Warning: Previous Freq
3 = Warning: Preset Freq
4 = Fault
5 = Fault, Coast
P9.2
12
4 mA Fault Frequency 0.00 Par. P1.2 Hz 0.00 331
P9.3
12
External Fault 2 307 See P9.11
P9.4
12
Input Phase Fault 2 332 See P9.11
P9.5
12
Uvolt Fault Response 2 330 See P9.11
P9.6
12
Output Phase Fault 2 308 See P9.11
P9.7
12
Ground Fault 2 309 See P9.11
P9.8
12
Motor Thermal Protection 2 310 See P9.11
P9.9
2
Motor Thermal F0 Current 0.0 150.0 % 40.0 311
P9.10
2
Motor Thermal Time 1 200 min 12 312
P9.11
12
Stall Protection 0 313 0 = No Action
1 = Warning
2 = Fault
3 = Fault, Coast
P9.12
2
Stall Current Limit 0.1 Active Motor
Nom I*2
A Active Motor Nom
I*13/10
314
P9.13
2
Stall Time Limit 1.0 120.0 s 15.0 315
P9.14
2
Stall Frequency Limit 1.00 Par. P1.2 Hz 25.00 316
P9.15
12
Underload Protection 0 317 See P9.11
P9.16
2
Underload Fnom Torque 10.0 150.0 % 50.0 318
P9.17
2
Underload F0 Torque 5.0 150.0 % 10.0 319
P9.18
2
Underload Time Limit 2.00 600.00 s 20.00 320
P9.19
12
Thermistor Fault Response 2 333 See P9.11
P9.20
2
Line Start Lockout 2 750 0 = Disabled, No Change
1 = Enable, No Change
2 = Disabled, Changed
3 = Enable, Changed
Table 71. Motor Control—P8, continued
Code Parameter Min. Max. Unit Default ID Note