Technical data
May 2007
CA05001001E For more information visit: www.eaton.com
61
PLC, I/O & Communications Products
IT. Connect
Communication Adapters (D77D Series) — PROFIBUS Adapter
Product Description
The Cutler-Hammer
®
Intelligent Tech-
nologies (IT.) PROFIBUS Adapter
(D77D-PNA) from Eaton’s electrical
business has greatly increased the
functionality of Cutler-Hammer IT.
communicating products, allowing
monitoring and control for IT. I/O and
IT. motor control devices. The adapter
concentrates all data from these
devices into a single node.
The PROFIBUS Adapter supports not
only PROFIBUS but also Modbus
(ASCII and RTU) as a slave device. This
combination of the two physical layers
provides for ultimate functionality
when connecting to a control system.
This unique feature of the D77D-PNA
provides for deterministic control
using PROFIBUS along with the flexi-
bility to monitor and configure I/O
devices over Modbus. The Modbus
connection is a read-only connection
not allowing control of I/O devices
ensuring a single point of control.
To simplify the configuration of the
D77D-PNA, a simple auto-configure
button press sets the system up for
default operation. This automatically
configures the telegrams to the system
devices.
Application Description
In a typical PROFIBUS Adapter applica-
tion, the D77D-PNA connects directly
to PROFIBUS, and resides in a system
with IT. I/O and other communicating
motor controls. The data from these
IT. devices is assembled into input
and output telegrams before being
presented.
Cat. No. D77D-PNA
Features, Functions and Benefits
■ Communication to PROFIBUS
consuming one address
■ Supports hardware addressing
■ DB9 Connection
■ Modbus slave connections on
motherboard
■ Provides for control of all IT. com-
municating devices connected to
the network adapter
■ PROFIBUS supports autobaud
■ Single button press auto configures
the gateway, setting up the system
for default operation
■ Advanced configuration using
CH Studio
■ Provides for backplane and inter-
connect cable connections to I/O
modules and motor control
products
■ Two independent ports for Plug-
and-Play connection to I/O
■ Powered from backplane
■ Isolated from PROFIBUS
■ Status LEDs for module health
■ Provides for configuration of I/O
devices over Modbus TCP
■ Small package size
■ DIN rail mountable
Standards and Certifications
Approvals
Table 94. Approvals/Certifications
Technical Data and Specifications
Table 95. Environmental Ratings Table 96. PROFIBUS Specifications
Description Specification
Electrical/EMC
ESD Immunity (IEC 61000-4-2) ± 8 kV air, ± 4 kV contact
Radiated Immunity (IEC 61000-4-3) 10V/m 80 – 1,000 MHz, 80% amplitude modulation @ 1 kHz
Fast Transient (IEC 61000-4-4) ± 2 kV supply and control, ± 1 kV communications
Surge (IEC 61000-4-5) ± 1 kV line-to-ground, ± 2 kV line-to-line
RF Conducted (IEC 61000-4-6) 10V, .15 – 80 MHz
Magnetic Field (IEC 61000-4-8) 30A/m, 50 Hz
Other Approvals
Ingress Protection Code IP20
Radiated and Conducted Emissions EN 5011 Class A
Agency Certifications UL 508, CUL (CSA C22.2 No. 14), CE (Low Voltage Directive),
Modbus Conformance Tested
Description Specification
Transportation/Storage
Temperature -58° – 176°F (-50° – 80°C)
Humidity 5 – 95% non-condensing
Operating
Temperature -13° –149 °F (-25° – 65°C)
Humidity 5 – 95% non-condensing
Altitude Above 6,600 ft. (2,000m)
consult factory
Shock
(IEC 68-2-27)
15G any direction for
11 mS
Vibration
(IEC 68-2-6)
5 – 150 Hz, 5G .7 mm
maximum peak-to-peak
Pollution Degree 2
Description Specification
Connection DB9
I/O Size 244 Bytes Input
176 Bytes Output
Baud Up to 12 Megabit
Addressing DIP Switch 1 – 255
Channels 2 Independent
Channels
CHA Current
Draw
170 mA
CHB Current
Draw
10 mA