Technical data
CA05001001E For more information visit: www.eaton.com
53
PLC, I/O & Communications Products
May 2007
IT. Connect
Starter Network Adapters (SNAP) (D77B Series) — QCPort SNAP
QCPort Starter Network
Adapter Product (QSNAP)
Product Description
The Cutler-Hammer
®
QCPort Starter
Network Adapter Product (QSNAP)
from Eaton’s electrical business is a
front-mount device providing commu-
nication capability, control and moni-
toring to Intelligent Technologies (IT.)
Electromechanical Starters, as well as
the S751 and S752 Soft Start, as listed
in Tables 76 – 78. The QSNAP allows
connection to any communications
adapter and provides access to any
support network.
The IT. QSNAP has an optional HANDS/
OFF/AUTO (HOA) module that enables
the starter to be operated in hand
mode; even if the QSNAP is not pow-
ered. The HOA option is used for cus-
tomers who need the extra security of
manual control in conjunction with
industrial network communication
capabilities.
With the addition of a D64 zero
sequence CT, the QSNAP can be
enabled to detect ground faults for
added protection.
Features
■ Starter/contactor connectivity con-
necting motor control and I/O on
same communication adapter
■ Configuration using a software
application is not required for nor-
mal operation
■ Advanced configuration using
CH Studio
■ Includes pre-wired starter intercon-
nect cable and terminal adapter
Comprehensive Motor Data and
Control
■ RMS average current
■ % of operating FLA
■ % thermal memory
■ Integral contact position detection
■ Operating status and fault codes
■ At speed (soft starters)
■ START/STOP control
■ RUN/FORWARD-REVERSE control
■ Trip Reset
Extended Starter Capabilities
■ Ground fault detection (with
accessory)
■ Fault log
■ Overcurrent warning (adjustable)
■ Undercurrent warning (adjustable)
■ Emergency stop detection
Figure 71. Typical QSNAP Application
Catalog Number D77B-QSNAP-X1
with 54 mm IT. Starter
IT.
Starters with QSNAPs
To Control
PC or PLC
D77D-EIP, D77D-EMA,
D77D-DNA, D77D-PNA
Table 76. IEC SNAP Connectivity
Table 77. NEMA SNAP Connectivity
Table 78. S751/S752 SNAP Connectivity
Application Description
A typical application for the QSNAP
will contain many QSNAPs and many
I/O products all connected to a single
network adapter. With this architec-
ture, an entire panel can be repre-
sented by a single network adapter.
IEC E101, E501
Frame Size Continuous
Ampacity
Rating
45 mm B 18 Amp
25 Amp
32 Amp
54 mm C 40 Amp
50 Amp
76 mm D 65 Amp
85 Amp
100 Amp
105 mm E 125 Amp
160 Amp
200 Amp
140 mm F 250 Amp
315 Amp
420 Amp
NEMA N101, N501
Size Continuous Ampacity
Rating
00 9
0 18
1 27
2 45
3 90
4 135
5 270
S751/S752 Soft Start
54 mm All Sizes