Specifications

February 2009
CA08102001E For more information visit: www.eaton.com
50-29
PLC, I/O & Communications Products
50
IT. Connect
Communication Adapters (D77D Series) — PROFIBUS Adapter
Cat. No. D77D-PNA
Product Description
The Cutler-Hammer Intelligent
Technologies (IT.) PROFIBUS Adapter
(D77D-PNA) from Eaton’s electrical
business has greatly increased the
functionality of Cutler-Hammer IT.
communicating products, allowing
monitoring and control for IT. motor
control devices. The adapter concen-
trates all data from these devices into
a single node.
The PROFIBUS Adapter supports not
only PROFIBUS but also Modbus
(ASCII and RTU) as a slave device. This
combination of the two physical layers
provides for ultimate functionality
when connecting to a control system.
This unique feature of the D77D-PNA
provides for deterministic control
using PROFIBUS along with the flexi-
bility to monitor and configure I/O
devices over Modbus. The Modbus
connection is a read-only connection
not allowing control of I/O devices
ensuring a single point of control.
To simplify the configuration of the
D77D-PNA, a simple auto-configure
button press sets the system up for
default operation. This automatically
configures the telegrams to the
system devices.
Application Description
In a typical PROFIBUS Adapter applica-
tion, the D77D-PNA connects directly
to PROFIBUS, and resides in a system
with communicating motor controls.
The data from these IT. devices is
assembled into input and output
telegrams before being presented.
Features, Functions and Benefits
Communication to PROFIBUS
consuming one address.
Supports hardware addressing.
DB9 Connection.
Modbus slave connections on
motherboard.
Provides for control of all IT.
communicating devices connected
to the network adapter.
PROFIBUS supports autobaud.
Single button press auto configures
the gateway, setting up the system
for default operation.
Advanced configuration using
CH Studio.
Provides for backplane and
interconnect cable connections
to motor control products.
Two independent ports.
Powered from backplane.
Isolated from PROFIBUS.
Status LEDs for module health.
Provides for configuration of I/O
devices over Modbus TCP.
Small package size.
DIN-rail mountable.
Standards and Certifications
Approvals
Table 50-42. Approvals/Certifications
Technical Data and Specifications
Table 50-43. Environmental Ratings Table 50-44. PROFIBUS Specifications
Description Specification
Electrical/EMC
ESD Immunity (IEC 61000-4-2) ± 8 kV air, ± 4 kV contact
Radiated Immunity (IEC 61000-4-3) 10V/m 80 – 1,000 MHz, 80% amplitude modulation @ 1 kHz
Fast Transient (IEC 61000-4-4) ± 2 kV supply and control, ± 1 kV communications
Surge (IEC 61000-4-5) ± 1 kV line-to-ground, ± 2 kV line-to-line
RF Conducted (IEC 61000-4-6) 10V, .15 – 80 MHz
Magnetic Field (IEC 61000-4-8) 30A/m, 50 Hz
Other Approvals
Ingress Protection Code IP20
Radiated and Conducted Emissions EN 5011 Class A
Agency Certifications UL 508, CUL (CSA C22.2 No. 14), CE (Low Voltage Directive),
Modbus Conformance Tested
Description Specification
Transportation/Storage
Temperature -58° – 176°F (-50° – 80°C)
Humidity 5 – 95% non-condensing
Operating
Temperature -13° –149 °F (-25° – 65°C)
Humidity 5 – 95% non-condensing
Altitude Above 6,600 ft. (2,000m)
consult factory
Shock
(IEC 68-2-27)
15G any direction for
11 mS
Vibration
(IEC 68-2-6)
5 – 150 Hz, 5G .7 mm
maximum peak-to-peak
Pollution Degree 2
Description Specification
Connection DB9
I/O Size 244 Bytes Input
176 Bytes Output
Baud Up to 12 Megabit
Addressing DIP Switch 1 – 255
Channels 2 Independent
Channels
CHA Current
Draw
170 mA
CHB Current
Draw
10 mA