Specifications

February 2009
CA08102001E For more information visit: www.eaton.com
50-25
PLC, I/O & Communications Products
50
IT. Connect
Communication Adapters (D77D Series) — Modbus Adapter
Cat. No. D77D-EMA
Product Description
The Cutler-Hammer Intelligent
Technologies (IT). Ethernet Modbus
Adapter (D77D-EMA) from Eaton’s
electrical business has greatly
increased the functionality of Cutler-
Hammer IT. communicating products,
allowing monitoring and control for IT.
motor control devices. The adapter
concentrates all data from these
devices into a single Modbus node.
The Modbus Adapter supports not
only Modbus TCP but also Modbus
serial (ASCII and RTU) as a slave
device. This combination of the two
physical layers provides for ultimate
functionality when connecting to a
Modbus system. A unique attribute
of the D77D-EMA is that it supports
Modbus serial Pass-Through. In this
mode a customer can connect Modbus
serial devices to one of the channels
and monitor and control them over
Modbus TCP.
To simplify the configuration of the
D77D-EMA, a simple auto-configure
button press sets the system up for
default operation. This automatically
configures the Modbus registers to the
I/O system devices.
Application Description
In a typical Modbus Adapter applica-
tion, the D77D-EMA connects directly
to Modbus, and resides in a system
with communicating motor controls.
The data from these IT. devices is
assembled into input and output
registers before being presented
to Modbus.
Features, Functions and Benefits
Communication to Modbus
consuming one address.
Supports Boot P and static
IP addressing.
10/100 BaseT Connection.
RS-485 Modbus slave serial
connection.
Supports Serial Modbus Pass-
Through over Modbus TCP.
Provides for control of all IT.
communicating devices connected
to the gateway.
Manually set to address and baud
rate for serial Modbus; configura-
tion using a software application is
not required for normal operation.
Single button press auto configures
the gateway, setting up the system
for default operation.
Advanced configuration using
CH Studio.
Provides for backplane and
interconnect cable connections
to motor control products.
Two independent ports.
Powered from backplane.
Isolated from Modbus.
Status LEDs for Modbus and
module health.
Provides for configuration of I/O
devices over Modbus TCP.
Small package size.
DIN-rail mountable.
Standards and Certifications
Approvals
Table 50-34. Approvals/Certifications
Technical Data and Specifications
Table 50-35. Environmental Ratings Table 50-36. Modbus Specifications
Description Specification
Electrical/EMC
ESD Immunity (IEC 61000-4-2) ± 8 kV air, ± 4 kV contact
Radiated Immunity (IEC 61000-4-3) 10V/m 80 – 1,000 MHz, 80% amplitude modulation @ 1 kHz
Fast Transient (IEC 61000-4-4) ± 2 kV supply and control, ± 1 kV communications
Surge (IEC 61000-4-5) ± 1 kV line-to-ground, ± 2 kV line-to-line
RF Conducted (IEC 61000-4-6) 10V, .15 – 80 MHz
Magnetic Field (IEC 61000-4-8) 30A/m, 50 Hz
Other Approvals
Ingress Protection Code IP20
Radiated and Conducted Emissions EN 5011 Class A
Agency Certifications UL 508, CUL (CSA C22.2 No. 14), CE (Low Voltage Directive),
Modbus Conformance Tested
Description Specification
Transportation/Storage
Temperature -58° – 176°F (-50° – 80°C)
Humidity 5 – 95% non-condensing
Operating
Temperature -13° –149 °F (-25° – 65°C)
Humidity 5 – 95% non-condensing
Altitude Above 6,600 ft. (2,000m)
consult factory
Shock
(IEC 68-2-27)
15G any direction for
11 mS
Vibration
(IEC 68-2-6)
5 – 150 Hz, 5G .7 mm
maximum peak-to-peak
Pollution Degree 2
Description Specification
Connections 10/100 BaseT
RS-485
I/O Size 1024 Registers Input
1024 Registers Output
Baud Ethernet 10 Megabit
Serial 1200 to 115.2K baud
Addressing Ethernet – Boot P or Static IP
Serial – DIP Switch 1 – 255
Channels 2 Independent
Channels