Setup guide

MN03902004E 5 November 2006
Figure 11: Basic Connection Diagram for 24V DC
3-Wire Pushbutton STOP/START/JOG/RESET
and 24V DC Fault/Ready and Bypass Indication
Figure 12: Basic Connection Diagram for 24V DC 2-Wire Switch
HAND/OFF/AUTO(Remote Contact)/RESET
and 24V DC Fault/Ready and Bypass Indication
Figure 13: Basic Connection Diagram for Use of DIM Control Only
Note:
1. A minimum of wire of 14 AWG (2.5 mm
2
) should be
used between the power supply and the 24V DC + and -
terminals.
2. See User Manual if it is desired to use a relay instead of
an indicating lamp for terminals 13, 14, 95, 96 and 98.
3. The start input TB #1 default is set for level sense – See
User Manual.
24V DC
Power Supply
Jumper
+24V to 3
98
96
95
14
13
3
4
2
1
P
+
S811 Soft Starter
+
24V DC Power
Internal
Contacts
Optional 24V DC
Pilot Lights
(See Note 2)
Stop
Start
E-Stop
Jog
Reset
In Bypass
Ready
Fault
Inputs
24V DC Only
(See Note 3)
* E-Stop Maintained
(See Note 1)
*
24V DC
Power Supply
Jumper
+24V to 3
98
96
95
14
13
3
4
2
1
P
+
S811 Soft Starter
+
24V DC Power
Internal
Contacts
Optional 24V DC
Pilot Lights
(See Note 2)
(See Note 1)
(See Note 3)
* E-Stop Maintained
Reset
In Bypass
Ready
Fault
Inputs
24V DC Only
Jumper
Remote
Contact
Hand
Auto
OFF
E-Stop
*
Caution
Only apply 24V DC to the terminal block unless specified otherwise in this
manual. All control wiring is 22 – 12 AWG (0.33 – 2.5 mm
2
). Failure to follow this
caution could result in severe damage to the controller.
Attention
Appliquer seulement 24V CC à la barrette à bornes sauf ce manuel offre d’avis
contraire. Tout le câblage de commande est de calibre 0,33 – 2,5 mm
2
(22 –
12 AWG). L’inobservation de cet énoncé pourrait entraîner des dégâts matériels
au contrôleur.
Precaución
Aplique sólo 24 V CC al bloque de terminales, a menos que se especifique lo
contrario en este manual. Todo el cableado de control es de 0.33 – 2.5 mm
2
(22 – 12 AWG). Si no respeta esta precaución, se pueden producir daños graves
al controlador.
24V DC
Power Supply
Jumper
+24V to P
98
96
95
14
13
3
4
2
1
P
+
S811 Soft Starter
+
24V DC Power
Internal
Contacts
E-Stop
Inputs
24V DC Only
(See Note 1)
*
* E-Stop Maintained
MN03902004E.fm Page 5 Tuesday, November 28, 2006 8:49 AM