Setup guide

MN03902004E 13 November 2006
ENTER
ESC
PREV
ONLN SS OXFDO1 H STOP
Protection Setup
NEXT ENTER
ESC
Protection Setup Menu 5
Parameter Units Min Max Default Access
Level
1 Phase Sequence 0102
2 Phase Rev Fault 0102
3 Motor Rated Volt Volts 115 600 480 2
4 Low Volt Trip 0112
5 Low Volt Level % 1 99 90 2
6 Low Volt Trip Dly Sec 1 60 3 2
7 Hi Volt Trip 0112
8 Hi Volt Level % 101 120 110 2
9 Hi Volt Trip Dly Sec 1 60 3 2
10 V Imbal Trip Lev % 1 100 6 2
11 V Imbal Trip Dly Sec 1 60 0.5 2
12 Phase Loss Fault 0112
(Continued at right)
Protection Setup (Continued) Menu 5
Parameter Units Min Max Default Access
Level
13 Phase Loss % Trp % 1 100 80 2
14 Phase Loss Trip Dly Sec 1 60 0.5 2
15 Low I Trip % FLA % 0 100 6 2
16 Phase Imb Fault 0112
17 I Imbal Trip Lev % 1 100 40 2
18 I Imbal Trip Dly Sec 1 60 0.5 2
19 SCR Short Fault 0112
20 SCR Conduct Fault 0112
21 Jam Fault 0112
22 Stall Fault 0112
23 Temp Sense Fault 0112
MN03902004E.fm Page 13 Tuesday, November 28, 2006 8:49 AM