User manual

Intelligent Technologies (IT.) QSNAP
12
Pub. No. MN05001001E
February 2002
Table 11: Default Input Data
Output Data
Use Tables 12 and 13 when setting up the QSNAP output data.
Table 12: Default Output Data
Table 13: Output Assembly Data Definitions
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
3-Phase Average RMS Current LSB Byte 0
3-Phase Average RMS Current Byte 1
3-Phase Average RMS Current Byte 2
3-Phase Average RMS Current MSB Byte 3
% Thermal Capacity LSB Byte 4
% Thermal Capacity MSB Byte 5
Fault/Warning Codes LSB Byte 6
Fault/Warning Codes MSB Byte 7
Reserved Warning Faulted Local
Control
Resetting Permissive Running 2 Running 1 Byte 8
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Reserved Reserved Local
Control
Local /
Remote
Fault
Reset
Permissive Run 2 Run 1 Byte 8
Data Description
Run 1 Energize the rst starter when Permissive is 1
Run 2 Energize the second starter when Permissive is 1
Fault Reset Reset the fault
Permissive Starter Permissive, O Stops the starter, I Enables to run the starter