Serial Pass-Through Mode
NOTE Serial pass-through functionality is available only with the ConnectUPS Card
firmware v3.20 and higher (with older, non-RoHS hardware) and v4.20 and higher (with RoHS
hardware). Updates to the ConnectUPS Card firmware are available at
http://powerquality.eaton.com/Support/Software-Drivers/default.asp.
During normal operation, the ConnectUPS Card controls the
communication path to the UPS and allows network-based access to
UPS data through the Web and SNMP. Some situations require direct
serial communication to the UPS in a pass-through mode, such as:
S The UPS firmware requires a field upgrade with a 9600 baud serial
port connection to the UPS.
S The user wants to run a local copy of LanSafe software with serial
communication to the UPS.
The card's Normal mode of operation must be disabled for Serial
Pass-Through mode to be available.
Reconfiguring the Card for Serial Pass-Through Mode
NOTE In Serial Pass-Through mode, communication through the ConnectUPS Card Ethernet
port stops, and any existing connections (such as to NetWatch software clients or SNMP
management tools) cease. However, the Ethernet switch functionality of the ConnectUPS
Card continues to function.
The following steps disable Normal mode by changing the switches on
the ConnectUPS Card and restarting the card in Serial Pass-Through
mode.
To reconfigure the card for Serial Pass-Through mode:
1. Note the current position of DIP switches on the card [the default
setting for both switches is the 0 (off) position]. Write them here for
later reference.
DIP Switch 1 _____ 0 (off) _____ 1 (on)
DIP Switch 2 _____ 0 (off) _____ 1 (on)
2. Set both DIP switches to the 1 (on) position for Serial Pass-Through
mode.