SPD Type 2 plug-on surge protection—UL 1449 3rd Edition
Catalog
number Description Connection Voltage Phase
Frequency
(Hz) MCOV
A
VPR
B
I
n
C
SCCR
D
Surge
current
capacity,
per phase
rating
E
BRSURGE UL for use in a single-phase
Type BR loadcenter
Plug on to the loadcenter
bus; see instructions
120/240 Vac Single 60 150 V L1–N,
300 V L–L
600 V L1–N,
1000 V L–L
3 kA 10 kA 18 kA
CLSURGE This unit is classified by UL
for use in select GE, ITE/
Siemens and Crouse-Hinds
panels (refer to Pub. No.
5655B65H01 for additional
details)
Plug on to the loadcenter
bus; see instructions
120/240 Vac Single 60 150 V L1–N,
300 V L–L
600 V L1–N,
1000 V L–L
3 kA 10 kA 18 kA
CHSA UL and CSA for use in a
Type CH loadcenter
Plug on to the loadcenter
bus; see instructions
120/240 Vac Single 60 150 V L1–N,
300 V L–L
600 V L1–N,
1000 V L–L
3 kA 10 kA 18 kA
BRSURGECSA CSA for use in an Eaton
Type BR loadcenter
Plug on to the loadcenter
bus; see instructions
120/240 Vac Single 60 150 V L1–N,
300 V L–L
600 V L1–N,
1000 V L–L
3 kA 10 kA 18 kA
CHQSA This device is UL classified
to be used in place of
Square D Type QO surge
arresters (refer to Pub-23974)
Plug on to the loadcenter
bus; see instructions
120/240 Vac Single 60 150 V L1–N,
300 V L–L
600 V L1–N,
1000 V L–L
3 kA 10 kA 18 kA
A
MCOV: Maximum continuous operating voltage that may be applied to the device per mode.
B
VPR: Voltage protection rating is the measured limiting voltage after a surge event.
C
I
n
: Nominal discharge current is the current that the device can withstand for 15 impulses.
D
SCCR: The amount of current the product can withstand under short-circuit conditions.
E
Surge current capacity: The maximum one-time surge current rating per phase.
ote:N For warranty details, go to www.eaton.com/surgetrap.
Compatibility list for classied applications
The Eaton surge protective device has been classified by UL for use in the listed panelboards below.
System Supply
Listed panelboards
Crouse-HindsE General ElectricT ITE/SiemensT
Single-phase
Three-wire
120/240 V~
Maximum short-circuit current 10 kA
LC112DF/DS
LC116DF/DS
LC120DF/DS
LC220EC/PC
LC224EC/PC
LC230EC/PC
LC236PC
LC240PC
JA112CW
JA112CY
JA224CY
JA222CW
TM2010C/R
TM1212C/CT
2TM2020C/CT/R
TLM612F/S/R
TLM812F/S/R
TLM3020C/R
G2020MB1100
G2040MB1200
G2440MB1200
G3040MB1200
G3030MB1200
E612ML1125CU
W0612ML1125CU
E08112ML1225CU
W0812ML1125CU
E0816ML1125CU
W0816ML1125CU
ote:N Also suitable for use in all plug-on WestinghouseT/Eaton Cutler-Hammer series (Type BR), Bryant, Challenger and General Switch panelboards.
Follow us on social media to get the
latest product and support information.