Datasheet
08/04/2017 017527 - HPL-ED2017 V34.0 EN 3 / 4
Surface finish Galvanized
Passivated
Material�characteristics
Material glass-fibre reinforced polycarbonate (base)
non-reinforced polycarbonate (cover)
Halogen free
Surface finish Galvanized
Passivated
Colour RAL 7032, pebble grey (base)
transparent, opaque (cover)
Colour
Base RAL 7032, pebble grey
Housing body Transparent, colourless or RAL 7032, pebble grey
Material�properties
Electrical
Track resistance KB160, KC175 (base, to IEC 60112)
KB100, KC200 (cover, to IEC 60112)
Surface resistance to IEC 60093
Ω x 10
13
1
Dielectric strength to IEC 60243-1 kV/mm 30
Thermal
Temperature resistant -40 °C - 120 °C (enclosure)
85 °C (enclosure bolt)
80 °C (gasket)
Mechanical
Impact resistance IK10 according to EN 50102
Loading capacity
kg/m
2
10
Chemical resistance
Chemical resistant Resistant against: Acids < 10 %, mineral oil, alcohol, gasoline, greases, salt
solutions
Partly resistant to: Acids > 10 %
Not resistant to: alkalis, benzene
Atmospheric
Saline spray IEC 60068-2-11
UV resistance Beneath protective shield
Water consumption to DIN EN ISO 62 % 0.29
Flammability characteristics
Flammability classification according to UL94 V1 (base)
V2 (cover)
Design�verification�as�per�IEC/EN�61439
Technical data for design verification
Heat dissipation, at an ambient temperature of 35°C, delta T: 20 degrees,
calculated as per IEC 60890
Individual enclosure for wall mounting P
V
CO 20
Starting enclosure for wall mounting P
V
CO 19
Middle enclosure for wall mounting P
V
CO 18
Heat dissipation, at an ambient temperature of 35°C, delta T: 35 degrees,
calculated as per IEC 60890
Individual enclosure for wall mounting P
V
CO 41
Starting enclosure for wall mounting P
V
CO 39
Middle enclosure for wall mounting P
V
CO 37
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects
Lower part: 960 °C / cover: 850 °C; meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation Not relevant to indoor installations.
10.2.5 Lifting 10 kg per enclosure with support frame and lifting aid met; assembled and secured
as per the latest applicable instruction leaflet.